Inspections for the day of: Tuesday, October 18, 2016.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-03818 FIRE-Final Inspection10/18/201610/18/201610/18/2016 2:10:43 PMPFAIL
Provide stickers at both main exit doors, provide annual inspection for the fire extinguishers, repair or remove the non-functional and non-required exit signs.
FIR16-00658 INSP-Sprinkler Rough-in10/18/201610/18/201610/18/2016 2:07:19 PMPFAIL
Per on site discussion it appears that the min. bury depth has not been met. Piping can not be buried.

Pat-underground Phone #: ###-####
FIR16-00659 INSP-Sprinkler Rough-in10/18/201610/18/201610/18/2016 2:06:30 PMPFAIL
Per on site discussion it appears that the min. bury depth has not been met. Piping can not be buried.

Pat-underground Phone #: ###-####
BLD15-04521 FIRE-Final Inspection10/17/201610/18/201610/18/2016 1:57:34 PMAFAIL
Provide ADA compliant hardware for the restrooms and second floor server room. Provide annual inspection for the fire extinguishers.
BLD16-03768 FIRE-Final Inspection10/17/201610/18/201610/18/2016 11:21:35 AMAFAIL
Provide exit signs with battery backup at all three doors per the approved plans, provide emergency lighting per the approved plans, provide panic hardware as per the approved plans, provide corrected occupant load sign, provide exit discharge emergency lighting per review note #6, provide code compliant exit from the Patio per the review comments, provide ADA approved hardware for the Office door.
BLD15-00371 FIRE-Final Inspection10/17/201610/18/201610/18/2016 8:43:02 AMAPASS
Life safety passed.