FIR15-00382
| INSP-Conference | 10/11/2017 | 10/16/2017 | | A | |
|
|
Follow up with Colton
|
FIR16-00446
| INSP-Alarm Testing | 10/17/2017 | 10/18/2017 | 10/18/2017 2:10:53 PM | P | DONE |
|
|
We set off the alarms and it mistakenly set off the alarms and shunted the elevator in the ajoining building. Testing was stopped and agreed to reschedule for tomorrow morning.
Phone #: ###-#### Inspection requested via web by Stacie Tasker
|
FIR17-00499
| INSP-Sprinkler Rough-in | 10/18/2017 | 10/18/2017 | 10/18/2017 2:08:48 PM | P | PART |
|
|
See the city approved plans for the two rooms where piping is ok to cover. An additional head is needed in the Storage room as shown on the plans.
Rick Phone #: ###-####
|
FIR17-00188
| INSP-Final Inspection | 10/17/2017 | 10/18/2017 | 10/18/2017 2:07:53 PM | P | PASS |
|
|
Permit finaled.
Peter Phone #: ###-####
|
BLD17-03543
| FIRE-Final Inspection | 10/17/2017 | 10/18/2017 | 10/18/2017 2:07:35 PM | A | PASS |
|
|
life safety passed.
Janett Phone #: ###-####
|
NAF17-00040
| INSP-Final | 10/18/2017 | 10/18/2017 | 10/18/2017 10:51:45 AM | P | DONE |
|
|
life safety passed. the sprinkler system has been removed as per agreement
Call prior to going Phone #: 8018652758 >> Inspection requested via mobile web by Ben johnson
|
FIR16-00284
| INSP-Sprinkler Rough-in/Hydro | 10/18/2017 | 10/18/2017 | 10/18/2017 10:01:09 AM | P | PASS |
|
|
200 psi Hydro test on dry system passed
|
BLD17-02385
| FIRE-Final Inspection | 10/17/2017 | 10/18/2017 | 10/18/2017 8:47:29 AM | A | FAIL |
|
|
All items have been corrected except the exit signs and emergency lighting still has issues.
|
BLD17-02686
| FIRE-Final Inspection | 10/17/2017 | 10/18/2017 | 10/18/2017 8:46:40 AM | A | PASS |
|
|
Life safety passed
Angel Phone #: ###-####
|