Inspections for the day of: Wednesday, October 18, 2017.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-00105 FIRE-Final Inspection10/17/201710/18/201710/18/2017 3:04:18 PMPPART
Fire sprinkler inspection for TCO complete, fire alarm inspection for TCO complete, commercial hood fire suppression system inspection for TCO complete, fire extinguishers are in place with a current inspection tags. TCO for life fire safety authorized for 90 days per conversation with Angela Brosious ###-####.
FIR17-00214 INSP-Final Inspection10/18/201710/18/201710/18/2017 3:00:49 PMPPART
Fire sprinkler inspection for TCO complete.
FIR17-00280 INSP-Final Inspection10/18/201710/18/201710/18/2017 3:00:21 PMPPART
Fire alarm inspection for TCO complete.
FIR17-00534 INSP-Final Inspection10/17/201710/18/201710/18/2017 2:57:13 PMPPASS
Fianl inspection for scope of work passed/complete.
FIR17-00308 INSP-Final Inspection10/17/201710/18/201710/18/2017 2:00:27 PMPFAIL
Flow switch would not activate on waterflow.
FIR17-00030 INSP-Final Inspection10/16/201710/18/201710/18/2017 1:41:55 PMAFAIL
Fire sprinkler head in middle level east room by stairs needs to be relocated, fire sprinkler head is currently 24 inches off of the center of the ceiling fan. Fire sprinkler head located in the west bathroom will need to be changed to an intermediate temperature head, sprinkler head is closer than 24 inches to heat source. Provide documentation showing that the spray in foam insulation is compatible with CPVC. Sheetrock needs to be installed over the exposed CPVC in the small storage room off of the garage. Irriigation was not installed at time of inspection, need to verify that the irrigation water (Irrigation water is supplied from the domestic feed) supply shuts off when flow switch activates.
BLD17-02178 FIRE-Final Inspection10/17/201710/18/201710/18/2017 9:47:03 AMAPASS
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher is mounted with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
FIR17-00497 INSP-Final Inspection10/17/201710/18/201710/18/2017 9:44:40 AMAPASS
Final fire sprinkler inspection for area of work passed/complete.
FIR16-00194 INSP-Sprinkler Rough-in/Hydro10/17/201710/18/201710/18/2017 9:24:52 AMACANC
We will have it pumped up around ten am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
FIR17-00473 INSP-Sprinkler Rough-in10/17/201710/18/201710/18/2017 9:17:50 AMAPART
Rough to cover inspection complete for level 1, noted the city approved drawings with yellow highlighter/red ink areas approved for cover.
FIR17-00573 INSP-Final Inspection10/17/201710/18/201710/18/2017 8:55:29 AMAPASS
Final fire alarm inspection for area of work passed/complete.
FIR17-00463 INSP-Final Inspection10/17/201710/18/201710/18/2017 8:53:49 AMAPASS
Final fire alarm inspection for area of work passed/complete.