ELE04-03218
| Rough-In Permanent Service | 10/18/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson r/i ok unfinished basement,, called about clearence closet fixture p/s u/g new ok 10/19/2004 8:30:33 AM
|
ELE04-02963
| Electrical Rough-In | 10/19/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | A | PART |
|
|
pantry light, iron circuit a/c conduit. thanx jack; Phone #: ###-#### Internet Inspection Request from: joe wheeler ok 10/19/2004 8:43:18 AM
|
ELE04-03214
| Rough-In Permanent Service | 10/18/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | A | FAIL |
|
|
craig ###-#### cor. posted called left message needs lights for inside for panel, 250.8 no SMS plugs that bond metal, 110.14,110.3(A) wire ringed and damaged panels and meterbase, 250.32 pick a method 250.32(B)(1),or (B)(2) 10/19/2004 10:02:36 AM
|
ELE04-03214
| Final | 10/18/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | A | NR |
|
|
craig ###-#### no power 10/19/2004 9:53:52 AM
|
ELE04-03215
| Rough-In Permanent Service | 10/18/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | A | FAIL |
|
|
criag ###-#### see comments for PM# ele04-03214 cor. posted 10/19/2004 10:03:35 AM
|
ELE04-03215
| Final | 10/18/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | A | NR |
|
|
craig ###-#### no power 10/19/2004 9:54:03 AM
|
ELE04-03213
| Conference | 10/18/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | P | DONE |
|
|
Scheduled by a contractor via Hello! on 10/18/2004 at 4:35:52 PM. Contact: ###-####. ok needs to uncover u/g covered before inspection 10/19/2004 3:07:27 PM
|
ELE04-01825
| Permanent Service | 10/19/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g new ok 10/19/2004 11:04:39 AM
|
ELE04-03224
| Temporary Service | 10/19/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | P | FAIL |
|
|
lars ###-#### cor. posted clean dirt from t/s seal KOs, use manufactures listed breakers only, use green or bare GEC called 10/19/2004 3:06:47 PM
|
ELE04-03216
| Temporary Service | 10/19/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | P | PASS |
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok t/s o/h new ok 10/19/2004 3:37:47 PM
|
ELE04-02797
| Electrical Rough-In | 10/19/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | P | PART |
|
|
gerad underground; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok pole lights and phone 10/19/2004 2:01:41 PM
|
ELE04-03230
| Final | 10/19/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | P | CANC |
|
|
stephen ###-#### called this is a t/s for 10-20-04 AM and north, not west contractor will reschedule there was some kind of mix up 10/19/2004 1:39:16 PM
|
ELE04-03234
| Final | 10/19/2004 | 10/19/2004 | 10/19/2004 12:00:00 AM | P | CANC |
|
|
###-#### - john contractor called and canceled 10/19/2004 1:08:40 PM
|