ELE05-02523
| Final | 10/19/2005 | 10/19/2005 | 10/20/2005 8:41:45 AM | A | FAIL |
|
|
cor. called shall ID white in uf cable as phase wire, and grd all poles at handhole
|
ELE05-02523
| Final | 10/18/2005 | 10/19/2005 | 10/19/2005 4:16:31 PM | P | PART |
|
|
ANY QUESTIONS PLEASE ED SCHALLOCK A CALL.; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
|
ELE05-02980
| ELE-Aging Inspection | 10/19/2005 | 10/19/2005 | 10/19/2005 2:40:45 PM | | PART |
|
|
called left message, no response
|
ELE05-03814
| Temporary Service | 10/19/2005 | 10/19/2005 | 10/19/2005 1:56:45 PM | P | PASS |
|
|
###-#### - nicole t/s u/g new ok
|
ELE05-03507
| Rough-In Permanent Service | 10/19/2005 | 10/19/2005 | 10/19/2005 1:43:32 PM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no r/i p/s o/h new ok
|
ELE05-03705
| Rough-In Permanent Service | 10/19/2005 | 10/19/2005 | 10/19/2005 1:06:48 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot cor. do not cover , called 210.52(A) required outlets all locations and fixed panel of slider door, 300.4 nail plates and 11/4" for all high and low voltage,, 314.16 correct box fill, note complete all required make up of boxes
|
ELE05-03764
| Temporary Service | 10/18/2005 | 10/19/2005 | 10/19/2005 10:31:26 AM | A | PASS |
|
|
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis t/s u/g new ok
|
ELE05-03784
| Temporary Service | 10/18/2005 | 10/19/2005 | 10/19/2005 10:31:01 AM | A | PASS |
|
|
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis t/s u/g new ok
|
ELE05-03767
| Temporary Service | 10/18/2005 | 10/19/2005 | 10/19/2005 10:30:23 AM | A | PASS |
|
|
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis t/s u/g new ok
|
ELE05-03381
| Electrical Rough-In | 10/18/2005 | 10/19/2005 | 10/19/2005 10:23:16 AM | A | PASS |
|
|
underground for post light//jim; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok
|
ELE05-03577
| Permanent Service | 10/18/2005 | 10/19/2005 | 10/19/2005 10:06:03 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty they need to change address to 2950 not 2954
|
ELE05-03795
| Final | 10/18/2005 | 10/19/2005 | 10/19/2005 9:41:53 AM | A | FAIL |
|
|
###-#### - john cor. called 250.8 no SMS,250.119&200.6 shall not ID #6 grds or neutrals shall be green and white, needs gfci for all recepts by spa
|
ELE05-00746
| Final | 10/17/2005 | 10/19/2005 | 10/19/2005 8:57:02 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer
|
ELE05-03669
| Electrical Rough-In | 10/18/2005 | 10/19/2005 | 10/19/2005 8:29:32 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/18/2005 at 3:28:20 PM. Contact: ###-####. u/g 1st floor panel rm
|
ELE05-03029
| ELE-Aging Inspection | 10/19/2005 | 10/19/2005 | 10/19/2005 7:36:36 AM | | NR |
|
|
|
ELE05-00504
| ELE-Aging Inspection | 10/19/2005 | 10/19/2005 | 10/19/2005 7:35:39 AM | | NR |
|
|
|