Inspections for the day of: Wednesday, October 19, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00406 INSP-Final Inspection10/18/200510/19/200510/19/2005 4:48:29 PMACANC
Inspection to be scheduled for 10/21 a.m.
BLD04-01076 FIRE-Final Inspection10/19/200510/19/200510/19/2005 4:47:48 PMPCANC
No time for inspection, will reschedule for tomorrow.
BLD04-01076 FIRE-Final Inspection10/19/200510/19/200510/19/2005 4:44:59 PMPCANC
FIR05-00462 INSP-Final Inspection10/18/200510/19/200510/19/2005 3:41:39 PMPFAIL
The manual pull station has not yet been replaced, the zoning has not been corrected, a lock at the FACP breaker has not been installed, inspection does not allow for time to amend these items while waiting on site, inspection to be rescheduled for 10/20 p.m.
FIR05-00663 INSP-Final Inspection10/19/200510/19/200510/19/2005 1:43:20 PMPPASS
Fire sprinkler passed inspection, permit finaled.
MIS05-00079 FIR-Final10/14/200510/19/200510/19/2005 1:40:15 PMPFAIL
Repair non-functioning emergency light at east exit, repair the main entry/exit doors so the panic hardware functions properly.
MIS05-00186 FIR-Final10/19/200510/19/200510/19/2005 1:00:56 PMPFAIL
Provide fire extinguishers in the garage and office areas as discussed, remove crossbar hardware at exit door from garage, provide approved hardware at door separating garage from office.
FIR05-00372 INSP-Sprinkler Rough-in/Hydro10/18/200510/19/200510/19/2005 12:11:53 PMAFAIL
The box office overhead hydro lost pressure to 197 psi., the UG supply hydro lost 5 psi., the standpipe, office depot shell area, and ann taylor area not tested at this time.
FIR05-00580 INSP-Conference10/18/200510/19/200510/19/2005 11:10:10 AMAFAIL
Provide the correct cd rating for the open office space strobe as required by the room dimentions, need to test EOL voltage drop, and verify signals.
BLD05-00989 FIRE-Final Inspection10/18/200510/19/200510/19/2005 10:13:24 AMAPASS
Fire life safety finaled.
FIR05-00467 INSP-Final Inspection10/19/200510/19/200510/19/2005 12:00:00 AMAPASS
Finaled.
FIR05-00467 DOC - Permit Finaled10/19/200510/19/200510/19/2005 12:00:00 AMPPASS
Fire sprinkler passed inspection.