Inspections for the day of: Thursday, October 19, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Schmer
TitleELE-CHIEF INSPECTOR
Phone #794-9423
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03884 Permanent Service10/19/200610/19/200610/19/2006 2:42:07 PMPPASS
p/s o/h rec ok jms
ELE06-00711 Electrical Rough-In10/19/200610/19/200610/19/2006 1:14:05 PMPCANC
Scheduled by a contractor via Hello! on 10/19/2006 at 8:14:30 AM. Contact: ###-####. rescedual for monday jms
ELE06-03877 Rough-In Permanent Service10/19/200610/19/200610/19/2006 1:08:01 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Paul Schepper p/s u/g new - ok
ELE06-03513 Electrical Rough-In10/19/200610/19/200610/19/2006 12:33:39 PMPPASS
UNDERGROUND INSPECTION; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy pole lts back - sign front undergrnd
ELE06-02081 Final10/18/200610/19/200610/19/2006 10:35:52 AMACANC
zane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles change to conference, service riser to small, grd. rods not connected right, grds to sub panels not installed properly, neutrals need identified and other corrections also. jms
ELE06-02364 Electrical Rough-In10/18/200610/19/200610/19/2006 9:50:09 AMAPASS
Scheduled by a contractor via Hello! on 10/18/2006 at 3:42:20 PM. Contact: ###-####. pool walls only
ELE06-03185 Rough-In Permanent Service10/18/200610/19/200610/19/2006 9:31:26 AMACANC
please inspect teh service so that idaho power can energize.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH chng to conference - needs fault current for service jms
ELE06-03865 Rough-In Permanent Service10/18/200610/19/200610/19/2006 9:02:03 AMAPART
steve; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i ok - p/s not ready jms