Inspections for the day of: Thursday, October 19, 2006.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03339 Electrical Rough-In10/19/200610/19/200610/19/2006 4:36:14 PMPPASS
tom Note: ceiling grid; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, told about ceiling wires for fixtures shall be straight, not at angle, ok to cover ceiling
ELE06-02780 Final10/19/200610/19/200610/19/2006 4:07:50 PMPFAIL
spencer; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 210.52(A) 2' wall in kitchen shall have recpt installed, 210.8(A)(7) recpt for washer shall be gfci, 410.4(D) fixture within 3' of shower area shall be listed for damp location, 408.4 circuit directory shall be clear, concise and detailed to load served, 440.12(A) a/c breakers shall be per nameplate on unit
ELE06-03881 Final10/19/200610/19/200610/19/2006 3:25:38 PMPPASS
Please call at least 30 mins prior to inspection so he can meet ya there///Spencer; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE06-03881 Permanent Service10/19/200610/19/200610/19/2006 2:55:12 PMPPASS
p/s o/h rec ok
ELE06-03824 Rough-In Permanent Service10/19/200610/19/200610/19/2006 2:37:26 PMPNR
Scheduled by a contractor via Hello! on 10/19/2006 at 10:36:02 AM. Contact: ###-####. met elect, called, left message, builder still has to build wall, elect still fixing corrections. Need to call when done.
ELE06-03867 Temporary Service10/19/200610/19/200610/19/2006 2:31:10 PMPPASS
corr made, t/s o/h n ok
ELE06-02104 Electrical Rough-In10/19/200610/19/200610/19/2006 2:18:58 PMPPART
Phone #: ###-#### Internet Inspection Request from: Don Lustig walls only and shop ceiling only ok to cover
ELE06-03787 Final10/19/200610/19/200610/19/2006 1:44:10 PMPCANC
ron; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see p/s
ELE06-03787 Permanent Service10/19/200610/19/200610/19/2006 1:43:37 PMPPASS
ron; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s u/g rec ok, will call for final ltr
ELE06-03823 Electrical Rough-In10/19/200610/19/200610/19/2006 1:10:25 PMPPASS
dustin; Phone #: ###-#### Internet Inspection Request from: Darla Downs corr made, ric ok
ELE06-01047 Final10/19/200610/19/200610/19/2006 10:56:38 AMAPASS
checked with contractor, job has been finalled, ok to final
ELE06-03867 Temporary Service10/19/200610/19/200610/19/2006 10:42:16 AMPCANC
Scheduled by a contractor via Hello! on 10/19/2006 at 10:02:06 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Oct 19 2006 10:42AM.
ELE06-01785 Electrical Rough-In10/18/200610/19/200610/19/2006 10:40:35 AMAFAIL
brandon Note: call for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called , left corr notice, nec 210.52(E) shall add 1 recpt for front of dwelling, 210.70(A) lighting outlet shall be added in kitchen, 110.12(A) unused openings in boxes shall be closed to provide equivalent protection as the wall of equipment, 110.12(C) wiring shall not be contaminated by foreign material such as paint, BCC address shall be posted
ELE06-03867 Temporary Service10/18/200610/19/200610/19/2006 10:00:49 AMAFAIL
Brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called, left message, left corr notice, nec 408.4 circuit directory shall be clear, concise, and explicit, 312.5 all conductors entering enclosures shall have abrasion protection, BCC job id sticker shall be posted
ELE06-03868 Temporary Service10/18/200610/19/200610/19/2006 9:50:09 AMAPASS
Lynn; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt t/s u/g n ok
ELE06-02718 Final10/18/200610/19/200610/19/2006 9:13:36 AMAPASS
mike - note: call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE06-03869 Electrical Rough-In10/18/200610/19/200610/19/2006 9:02:41 AMAPART
Eric, inspection on the underground floor boxes, please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover floor boxes only
ELE06-01888 Final10/18/200610/19/200610/19/2006 8:24:23 AMAPASS
Scheduled by a contractor via Hello! on 10/18/2006 at 1:50:30 PM. Contact: ###-####. ok to final
ELE06-03859 Electrical Rough-In10/18/200610/19/200610/19/2006 8:23:56 AMACANC
This is a reinspection because it failed. Everything is fixed so please let Luke know if something is not correct Bob. Thank you!; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL see rip
ELE06-03859 Rough-In Permanent Service10/19/200610/19/200610/19/2006 8:23:36 AMAPASS
This is a reinspection because it failed. Everything is fixed so please let Luke know if something is not correct Bob. Thank you!; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL corr made, ric ok, p/s u/g n ok
ELE06-03866 Permanent Service10/18/200610/19/200610/18/2006 2:49:41 PMAPASS
dan; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s o/h rec ok