ELE06-03339
| Electrical Rough-In | 10/19/2006 | 10/19/2006 | 10/19/2006 4:36:14 PM | P | PASS |
|
|
tom Note: ceiling grid; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, told about ceiling wires for fixtures shall be straight, not at angle, ok to cover ceiling
|
ELE06-02780
| Final | 10/19/2006 | 10/19/2006 | 10/19/2006 4:07:50 PM | P | FAIL |
|
|
spencer; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 210.52(A) 2' wall in kitchen shall have recpt installed, 210.8(A)(7) recpt for washer shall be gfci, 410.4(D) fixture within 3' of shower area shall be listed for damp location, 408.4 circuit directory shall be clear, concise and detailed to load served, 440.12(A) a/c breakers shall be per nameplate on unit
|
ELE06-03881
| Final | 10/19/2006 | 10/19/2006 | 10/19/2006 3:25:38 PM | P | PASS |
|
|
Please call at least 30 mins prior to inspection so he can meet ya there///Spencer; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
|
ELE06-03881
| Permanent Service | 10/19/2006 | 10/19/2006 | 10/19/2006 2:55:12 PM | P | PASS |
|
|
p/s o/h rec ok
|
ELE06-03824
| Rough-In Permanent Service | 10/19/2006 | 10/19/2006 | 10/19/2006 2:37:26 PM | P | NR |
|
|
Scheduled by a contractor via Hello! on 10/19/2006 at 10:36:02 AM. Contact: ###-####. met elect, called, left message, builder still has to build wall, elect still fixing corrections. Need to call when done.
|
ELE06-03867
| Temporary Service | 10/19/2006 | 10/19/2006 | 10/19/2006 2:31:10 PM | P | PASS |
|
|
corr made, t/s o/h n ok
|
ELE06-02104
| Electrical Rough-In | 10/19/2006 | 10/19/2006 | 10/19/2006 2:18:58 PM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Don Lustig walls only and shop ceiling only ok to cover
|
ELE06-03787
| Final | 10/19/2006 | 10/19/2006 | 10/19/2006 1:44:10 PM | P | CANC |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see p/s
|
ELE06-03787
| Permanent Service | 10/19/2006 | 10/19/2006 | 10/19/2006 1:43:37 PM | P | PASS |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s u/g rec ok, will call for final ltr
|
ELE06-03823
| Electrical Rough-In | 10/19/2006 | 10/19/2006 | 10/19/2006 1:10:25 PM | P | PASS |
|
|
dustin; Phone #: ###-#### Internet Inspection Request from: Darla Downs corr made, ric ok
|
ELE06-01047
| Final | 10/19/2006 | 10/19/2006 | 10/19/2006 10:56:38 AM | A | PASS |
|
|
checked with contractor, job has been finalled, ok to final
|
ELE06-03867
| Temporary Service | 10/19/2006 | 10/19/2006 | 10/19/2006 10:42:16 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/19/2006 at 10:02:06 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Oct 19 2006 10:42AM.
|
ELE06-01785
| Electrical Rough-In | 10/18/2006 | 10/19/2006 | 10/19/2006 10:40:35 AM | A | FAIL |
|
|
brandon Note: call for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called , left corr notice, nec 210.52(E) shall add 1 recpt for front of dwelling, 210.70(A) lighting outlet shall be added in kitchen, 110.12(A) unused openings in boxes shall be closed to provide equivalent protection as the wall of equipment, 110.12(C) wiring shall not be contaminated by foreign material such as paint, BCC address shall be posted
|
ELE06-03867
| Temporary Service | 10/18/2006 | 10/19/2006 | 10/19/2006 10:00:49 AM | A | FAIL |
|
|
Brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called, left message, left corr notice, nec 408.4 circuit directory shall be clear, concise, and explicit, 312.5 all conductors entering enclosures shall have abrasion protection, BCC job id sticker shall be posted
|
ELE06-03868
| Temporary Service | 10/18/2006 | 10/19/2006 | 10/19/2006 9:50:09 AM | A | PASS |
|
|
Lynn; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt t/s u/g n ok
|
ELE06-02718
| Final | 10/18/2006 | 10/19/2006 | 10/19/2006 9:13:36 AM | A | PASS |
|
|
mike - note: call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
ELE06-03869
| Electrical Rough-In | 10/18/2006 | 10/19/2006 | 10/19/2006 9:02:41 AM | A | PART |
|
|
Eric, inspection on the underground floor boxes, please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover floor boxes only
|
ELE06-01888
| Final | 10/18/2006 | 10/19/2006 | 10/19/2006 8:24:23 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 10/18/2006 at 1:50:30 PM. Contact: ###-####. ok to final
|
ELE06-03859
| Electrical Rough-In | 10/18/2006 | 10/19/2006 | 10/19/2006 8:23:56 AM | A | CANC |
|
|
This is a reinspection because it failed. Everything is fixed so please let Luke know if something is not correct Bob. Thank you!; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL see rip
|
ELE06-03859
| Rough-In Permanent Service | 10/19/2006 | 10/19/2006 | 10/19/2006 8:23:36 AM | A | PASS |
|
|
This is a reinspection because it failed. Everything is fixed so please let Luke know if something is not correct Bob. Thank you!; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL corr made, ric ok, p/s u/g n ok
|
ELE06-03866
| Permanent Service | 10/18/2006 | 10/19/2006 | 10/18/2006 2:49:41 PM | A | PASS |
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s o/h rec ok
|