Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02480 Final10/19/200710/19/200710/19/2007 2:52:56 PMPPASS
ok
ELE07-03254 Final10/19/200710/19/200710/19/2007 2:52:25 PMPPASS
Final Inspect on unit for Adair Homes Phone #: ###-#### Internet Inspection Request from: Charles pl no card
ELE07-03363 Final10/19/200710/19/200710/19/2007 1:56:48 PMPNH
Phone #: ###-#### Internet Inspection Request from: Alison Pennington called
ELE07-03473 Permanent Service10/19/200710/19/200710/19/2007 1:38:43 PMPPASS
Need inspection on new service and underground to detached garage, so existing service can be disconnected and be demolitioned, additionally we need the ufer inspected on the detached garage so it can be covered. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson
p/s u/g new ok
ELE07-03473 Electrical Rough-In10/19/200710/19/200710/19/2007 1:38:19 PMPPART
Need inspection on new service and underground to detached garage, so existing service can be disconnected and be demolitioned, additionally we need the ufer inspected on the detached garage so it can be covered. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson
u/g ok electrode ok for concrete
ELE07-01455 Final10/19/200710/19/200710/19/2007 12:42:28 PMPPASS
mitch - please call 1/2 hr prior to inspection Phone #: ###-#### ok card signed corr. made
ELE07-03542 Electrical Rough-In10/19/200710/19/200710/19/2007 11:55:09 AMPCANC
Please call Cevyn before inspection for instructions on getting in the house. thank you. ###-#### Phone #: ###-#### Internet Inspection Request from: Cevyn Recla contr. called and canceled request
ELE07-03525 Electrical Rough-In10/18/200710/19/200710/19/2007 10:05:55 AMAFAIL
Scheduled by a contractor via Hello! on 10/18/2007 at 8:36:06 PM. Contact: ###-####. corr called nail plates and 11/4", 210.11(C)(2) 20 amp laundry circuit shall only feeds recepts in laundry rm, 250.24 isolate grds and netrals basement sub panel (bond screw), 334.30 shall not staple romex on edge
ELE07-03469 Electrical Rough-In10/18/200710/19/200710/19/2007 9:02:30 AMAPASS
holly Note: please call 1/2 hr prior Phone #: ###-#### r/i ok told owner needs to replace box in hall upstairs box fill he will correct
ELE06-03105 ELE-Aging Inspection10/19/200710/19/200710/19/2007 8:23:10 AM DONE
ELE06-03105 Final10/19/200710/19/200710/19/2007 8:23:01 AMPPASS
ELE07-03393 Electrical Rough-In10/18/200710/19/200710/19/2007 8:14:17 AMACANC
Partial underground. Phone #: ###-#### Internet Inspection Request from: Todd Sellman contr. called and canceled