Inspections for the day of: Friday, October 19, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01399 ELE-Aging Inspection10/19/200710/19/200710/26/2007 2:47:20 PM DONE
see final
ELE06-01281 ELE-Aging Inspection10/19/200710/19/200710/22/2007 10:00:16 AM DONE
see final
ELE07-03580 Final10/19/200710/19/200710/19/2007 3:44:47 PMPPASS
butch Phone #: ###-#### ok to final
ELE07-03469 Electrical Rough-In10/19/200710/19/200710/19/2007 3:11:09 PMPPASS
holly Phone #: ###-#### garage only ok to cover, pointed out 3 places needing nail plates
ELE07-03553 Electrical Rough-In10/18/200710/19/200710/19/2007 2:48:42 PMPPASS
rough-in for kitchen remodel. Will be ready late afternoon, any questions call Jimmy @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose called contr to tie grounds together and verify 2' wall for receptacle by back door, ric ok kitchen, closet and bath wall only
ELE07-03492 Electrical Rough-In10/19/200710/19/200710/19/2007 2:01:09 PMPPASS
CALL PRIOR TO HEADING TO SITE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to pour slab anop
ELE07-03404 Permanent Service10/19/200710/19/200710/19/2007 1:06:25 PMPPASS
Final on new service, plus added wiring for new outlets and lights in garage and patio room. Phone #: ###-#### Internet Inspection Request from: Andy Rose ok to final, met contractor
ELE07-02790 Electrical Rough-In10/19/200710/19/200710/19/2007 12:28:43 PMPFAIL
rowdy Note: light conduit underground pool Phone #: ###-#### called, left correction notice, nec 352.26 there shall not be more than 4 quarter bends(360 degrees) total between pull points in rnc
ELE07-03576 Rough-In Permanent Service10/18/200710/19/200710/19/2007 9:48:32 AMAPASS
shawn Phone #: ###-#### ric ok shop and patio area, need to do kitchen area later, p/s rec u/g ok
ELE07-03492 Electrical Rough-In10/18/200710/19/200710/19/2007 9:00:14 AMANH
DAVE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called, left message, left card at trailer, do not know what supposed to inspect, said will have to recall
ELE07-03144 Final10/18/200710/19/200710/19/2007 8:28:52 AMAPASS
Brryan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final, signed occupancy card
ELE06-00711 Final10/19/200710/19/200710/19/2007 12:00:00 AMPPART
to is approved for area 1 basement,1st floor,2nd, 3rd 6th floor,7th floor,penthouse per Bill Thomas