Inspections for the day of: Friday, October 19, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00441 INSP-Final Inspection10/18/200710/19/200710/19/2007 4:57:36 PMAPART
Elevator testing completed, noted voltage monitoring to be supervisory, not an alarm condition as programed.
FIR07-00601 INSP-Sprinkler Rough-in10/18/200710/19/200710/19/2007 4:53:15 PMANR
don Phone #: ###-#### On site contact not available.
FIR07-00628 INSP-Final Inspection10/19/200710/19/200710/19/2007 4:50:27 PMPPASS
Fire alarm work passed per field inspection completed by M. Timmerman, permit finaled.
FIR07-00750 INSP-Final Inspection10/18/200710/19/200710/19/2007 3:45:57 PMPPASS
Fire sprinkler work completed satisfactory, inspection passed, permit finaled.
BLD06-01188 FIRE-Final Inspection10/17/200710/19/200710/19/2007 3:07:10 PMACANC
Overbooked.
FIR06-00595 INSP-Alarm Testing10/17/200710/19/200710/19/2007 3:06:41 PMACANC
Overbooked
FIR07-00694 INSP-Alarm Testing10/17/200710/19/200710/19/2007 2:59:47 PMAPART
contact person -Robert Phone #: ###-#### Internet Inspection Request from: Robert Gobler Final pending resolution of the tamper switch issue at the exisitng yard PIV between the two buildings.
FIR07-00856 INSP-Final Inspection10/18/200710/19/200710/19/2007 1:53:31 PMAPASS
Fire sprinkler permit work passed inspection, noted field changes are acceptable.
BLD07-00625 FIRE-Final Inspection10/18/200710/19/200710/19/2007 1:52:10 PMAFAIL
Need project related fire sprinkler final prior to life safety final approval, missing exit signs per plan review as red lined on approved building set, need suite address numbers, the new mag lock at the north main entry door failed to drop out upon alarm activation.
FIR07-00511 INSP-Final Inspection10/18/200710/19/200710/19/2007 1:48:58 PMAFAIL
Overspaced coverage due to missing upright heads at two locations in the SW corner of the tenant space, see plans for annotations, previously noted items are finished. Contractor is advised to complete a thorough field review of the installation prior to scheduling final inspection.
BLD07-01262 FIRE-Final Inspection10/19/200710/19/200710/19/2007 1:00:21 PMAPASS
Fire life safety passed.
FIR07-00864 INSP-Final Inspection10/18/200710/19/200710/19/2007 12:59:31 PMAPASS
Fire alarm work passed inspection, permit finaled.
FIR07-00330 FIR-Aging Inspection10/19/200710/19/200710/19/2007 8:17:13 AM DEFR
wip