Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00441 FIR-Aging Inspection10/19/200910/19/200910/20/2009 4:29:33 PM PEND
Pending site inspection request.
FIR09-00413 INSP-Sprinkler Rough-in10/19/200910/19/200910/19/2009 3:58:34 PMPPART
Final pending ceiling tile, escutcheons, hydrostatic test, C/N items.
FIR09-00523 INSP-Final Inspection10/19/200910/19/200910/19/2009 3:56:53 PMPNR
Rick- call 30 mins prior to going Phone #: ###-####
FIR09-00384 INSP-Sprinkler Rough-in/Hydro10/19/200910/19/200910/19/2009 3:56:31 PMPPART
See annotations on plan set marked with today's date for inspection notes including two blocked upright heads by adjacent truss web members, insulation at the deck needs lifted away from deflectors at two heads, install baffle or relocate two heads which exceed min. spacing. Discussed seismic bracing and coverage at the front entry vestibule. Noted correction items from the previous inspection are finished.
FIR09-00561 INSP-Sprinkler Rough-in/Hydro10/19/200910/19/200910/19/2009 3:51:38 PMAPART
Work in progress
FIR09-00476 INSP-Sprinkler Rough-in/Hydro10/19/200910/19/200910/19/2009 3:50:40 PMAPART
Okay to cover 1st floor as noted on stamped plan set.