Inspections for the day of: Friday, October 19, 2012.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00689 INSP-Final Inspection10/17/201210/19/201210/30/2012 9:34:34 AMAPART
Final walkthrough completed. Verify conditions per IFC 2009 1803.10.4 at the AE and FE ducts. Plan modifications meet field install.
FIR11-00645 INSP-Final Inspection10/17/201210/19/201210/30/2012 9:20:29 AMAPART
Final walkthrough completed acceptable for system 6 included in this permit.
FIR11-00431 INSP-Final Inspection10/17/201210/19/201210/30/2012 9:02:43 AMAPART
Re-inspection of previous C/N items.
FIR11-00365 INSP-Final Inspection10/17/201210/19/201210/30/2012 8:48:47 AMAPART
Re-inspection for noted C/N items
FIR11-00301 INSP-Final Inspection10/17/201210/19/201210/30/2012 8:42:26 AMAPART
Noted overspaced coverage at one location below ductwork at the junction between sub fab systems, provide verification AE and FE ductwork does not require protection per IFC 2009 1803.10.4 (1-3).
FIR11-00658 INSP-Final Inspection10/17/201210/19/201210/30/2012 7:48:06 AMAPASS
Previous C/N items finished.
FIR11-00524 INSP-Final Inspection10/17/201210/19/201210/30/2012 7:32:51 AMAPART
Field verified corrections.
FIR12-00102 INSP-Final Inspection10/17/201210/19/201210/30/2012 7:23:15 AMAPART
Plan modifications field verified to match installation and coverage adjustments.
FIR12-00189 INSP-Final Inspection10/17/201210/19/201210/30/2012 7:08:06 AMAPART
Pending coverage below ductwork obstructions.
FIR12-00523 INSP-Alarm Testing10/17/201210/19/201210/22/2012 2:03:09 PMPFAIL
Completed initial walkthrough- noted 9 locations in need of revision regarding notification appliances including both first and second floor levels (insp. completed 10/19).
FIR12-00451 INSP-Sprinkler Rough-in/Hydro10/19/201210/19/201210/22/2012 1:59:17 PMAPEND
BLD12-01193 FIRE-Final Inspection10/15/201210/19/201210/22/2012 1:58:41 PMPNR
BLD12-00575 FIRE-Final Inspection10/18/201210/19/201210/22/2012 1:58:10 PMAPASS
Fire life safety inspection passed.
BLD12-01055 FIRE-Final Inspection10/18/201210/19/201210/22/2012 1:55:04 PMANR
Pending project related FIR permit work.
FIR12-00314 INSP-Final Inspection10/18/201210/19/201210/22/2012 1:53:19 PMAFAIL
Dry system failed trip testing.
FIR12-00602 INSP-Final Inspection10/18/201210/19/201210/22/2012 1:51:22 PMAFAIL
PIV tamper not functional, low air in need of adjustment.
BLD11-02484 FIRE-Final Inspection10/16/201210/19/201210/19/2012 12:15:26 PMAPASS
Life safety passed provided door to remain... signage is posted and the manual thumbturn at the main entry/exit is removed. To be verified at structural final per discussion.