PLM14-02315
| PLM-Aging Inspection | 10/19/2015 | 10/19/2015 | 10/21/2015 6:50:52 AM | | PART |
|
|
No calls
|
PLM15-03602
| Groundwork | 10/19/2015 | 10/19/2015 | 10/19/2015 3:02:23 PM | P | PART |
|
|
Inspection requested via web by Brian Johansen-Partial trunkline ok to cover. Need to use an approved transition from abs to pvc from building drain to building sewer.
|
PLM15-03303
| Groundwork | 10/19/2015 | 10/19/2015 | 10/19/2015 2:59:14 PM | P | PART |
|
|
Inspection requested via web by Brian Johansen-Need to install all 3" san tees and 90's for toilets and retest before concrete. OK to cover.
|
MEC15-04572
| Pressure Test | 10/14/2015 | 10/19/2015 | 10/19/2015 2:55:51 PM | P | PASS |
|
|
Please call Daryl with any questions. Phone #: ###-#### Inspection requested via web by Diane Day-20 lb gas test pass
|
MEC15-04572
| Rough-in | 10/14/2015 | 10/19/2015 | 10/19/2015 2:54:40 PM | P | PASS |
|
|
Please call Daryl with any questions. Phone #: ###-#### Inspection requested via web by Diane Day
|
MEC15-04825
| Rough-in | 10/19/2015 | 10/19/2015 | 10/19/2015 1:33:38 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves-Duct sizing is not per the manual-j.
|
MEC15-04826
| Rough-in | 10/19/2015 | 10/19/2015 | 10/19/2015 1:32:52 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves-Duct sizing is not per the manual-j.
|
MEC15-04825
| Pressure Test | 10/19/2015 | 10/19/2015 | 10/19/2015 1:32:09 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves-20 lb gas test and flue test pass
|
MEC15-04826
| Pressure Test | 10/19/2015 | 10/19/2015 | 10/19/2015 1:31:31 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves-20 lb gas test and flue test pass
|
PLM15-03402
| Water and/or Sewer | 10/16/2015 | 10/19/2015 | 10/19/2015 11:38:28 AM | A | FAIL |
|
|
Ted Phone #: ###-####-Hose-clamps need to be 180 degrees from each other, blow out tee needs to be downstream of dbca and dbca needs tested and certified.
|
PLM15-03593
| Water and/or Sewer | 10/16/2015 | 10/19/2015 | 10/19/2015 11:29:52 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kirk Johns
|
PLM15-03592
| Water and/or Sewer | 10/16/2015 | 10/19/2015 | 10/19/2015 9:44:49 AM | A | PASS |
|
|
Building S, Units 101, 104, 105, 106 Phone #: ###-#### Inspection requested via web by Tom Maxwell
|
PLM15-03303
| Groundwork | 10/16/2015 | 10/19/2015 | 10/19/2015 9:34:51 AM | A | CANC |
|
|
|
PLM15-01841
| Final | 10/18/2015 | 10/19/2015 | 10/19/2015 9:25:21 AM | A | PASS |
|
|
Inspection requested via web by Kirk Johns
|
PLM15-03552
| Plumbing Rough-in | 10/16/2015 | 10/19/2015 | 10/19/2015 9:22:11 AM | A | PASS |
|
|
Allen Phone #: ###-####
|
PLM15-02687
| Final | 10/16/2015 | 10/19/2015 | 10/19/2015 8:21:02 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Branden Steers
|
PLM12-02999
| PLM-Aging Inspection | 10/19/2015 | 10/19/2015 | 10/19/2015 6:30:01 AM | | PART |
|
|
No calls
|