Inspections for the day of: Monday, October 19, 2015.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Strole
TitlePLM/MEC-INSPECTOR
Phone #794-7913
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM14-02315 PLM-Aging Inspection10/19/201510/19/201510/21/2015 6:50:52 AM PART
No calls
PLM15-03602 Groundwork10/19/201510/19/201510/19/2015 3:02:23 PMPPART
Inspection requested via web by Brian Johansen-Partial trunkline ok to cover. Need to use an approved transition from abs to pvc from building drain to building sewer.
PLM15-03303 Groundwork10/19/201510/19/201510/19/2015 2:59:14 PMPPART
Inspection requested via web by Brian Johansen-Need to install all 3" san tees and 90's for toilets and retest before concrete. OK to cover.
MEC15-04572 Pressure Test10/14/201510/19/201510/19/2015 2:55:51 PMPPASS
Please call Daryl with any questions. Phone #: ###-#### Inspection requested via web by Diane Day-20 lb gas test pass
MEC15-04572 Rough-in10/14/201510/19/201510/19/2015 2:54:40 PMPPASS
Please call Daryl with any questions. Phone #: ###-#### Inspection requested via web by Diane Day
MEC15-04825 Rough-in10/19/201510/19/201510/19/2015 1:33:38 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves-Duct sizing is not per the manual-j.
MEC15-04826 Rough-in10/19/201510/19/201510/19/2015 1:32:52 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves-Duct sizing is not per the manual-j.
MEC15-04825 Pressure Test10/19/201510/19/201510/19/2015 1:32:09 PMPPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves-20 lb gas test and flue test pass
MEC15-04826 Pressure Test10/19/201510/19/201510/19/2015 1:31:31 PMPPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves-20 lb gas test and flue test pass
PLM15-03402 Water and/or Sewer10/16/201510/19/201510/19/2015 11:38:28 AMAFAIL
Ted Phone #: ###-####-Hose-clamps need to be 180 degrees from each other, blow out tee needs to be downstream of dbca and dbca needs tested and certified.
PLM15-03593 Water and/or Sewer10/16/201510/19/201510/19/2015 11:29:52 AMAPASS
Phone #: ###-#### Inspection requested via web by Kirk Johns
PLM15-03592 Water and/or Sewer10/16/201510/19/201510/19/2015 9:44:49 AMAPASS
Building S, Units 101, 104, 105, 106 Phone #: ###-#### Inspection requested via web by Tom Maxwell
PLM15-03303 Groundwork10/16/201510/19/201510/19/2015 9:34:51 AMACANC
PLM15-01841 Final10/18/201510/19/201510/19/2015 9:25:21 AMAPASS
Inspection requested via web by Kirk Johns
PLM15-03552 Plumbing Rough-in10/16/201510/19/201510/19/2015 9:22:11 AMAPASS
Allen Phone #: ###-####
PLM15-02687 Final10/16/201510/19/201510/19/2015 8:21:02 AMAPASS
Phone #: ###-#### Inspection requested via web by Branden Steers
PLM12-02999 PLM-Aging Inspection10/19/201510/19/201510/19/2015 6:30:01 AM PART
No calls