Inspections for the day of: Monday, October 19, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00757 FIR-Aging Inspection10/19/201510/19/201510/27/2015 9:10:45 AM NR
Contractor is out of business
FIR14-00496 INSP-Final Inspection10/19/201510/19/201510/19/2015 3:23:19 PMPPASS
Permit finaled
BLD15-01780 FIRE-Conference10/19/201510/19/201510/19/2015 2:32:41 PMPDONE
Discussed bollard placement with Nate. The bollards at either end are spaced too far apart and all of the bollards, per Nate, will be less than 3'-0" to the equipment which does not meet IFC 312
FIR15-00479 INSP-Sprinkler Rough-in10/19/201510/19/201510/19/2015 2:07:16 PMPPASS
See the city approved plans for locations where the sprinkler piping can be covered.
BLD14-02369 FIRE-Final Inspection10/19/201510/19/201510/19/2015 12:49:48 PMPPASS
Life Safety Passed
BLD15-00701 FIRE-Final Inspection10/19/201510/19/201510/19/2015 12:47:38 PMPPASS
Life Safety Passed
FIR15-00533 INSP-Supply line flush10/16/201510/19/201510/19/2015 11:08:21 AMAPASS
Underground flush passed
BLD15-03734 FIRE-Final Inspection10/16/201510/19/201510/19/2015 10:41:46 AMAPASS
Life safety passed. Review did not address any equipment
FIR15-00536 INSP-Supply line flush10/16/201510/19/201510/19/2015 10:30:18 AMAPASS
Underground flush passed
BLD15-03693 FIRE-Final Inspection10/16/201510/19/201510/19/2015 10:29:18 AMAFAIL
Provide two fire extinguishers as discussed, remove the book shelves or provide additional exit signs and emergency lights as discussed, fill the combustible concealed space below the stage with non-combustible insulation as discussed. Revised scope of work may be needed due to construction of the stage.
FIR15-00479 INSP-Sprinkler Rough-in10/19/201510/19/201510/19/2015 9:53:23 AMPCANC
Storage and tenant areas
Please call Leroy 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt