Inspections for the day of: Monday, October 19, 2015.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00724 INSP-Alarm Testing10/19/201510/19/201510/19/2015 3:04:04 PMAPART
Fire alarm interface with heat tracing panels that monitor heat trace of fire sprinkler piping exposed to cold temps. See FIR 13-00461 for details of heat trace inspection.
FIR13-00178 INSP-Alarm Testing10/19/201510/19/201510/19/2015 3:01:19 PMAPART
Fire alarm interface with heat tracing panels that monitor heat trace of fire sprinkler piping exposed to cold temps. See FIR 13-00461 for details of heat trace inspection.
FIR13-00461 INSP-Alarm Testing10/19/201510/19/201510/19/2015 2:58:25 PMPPART
Test of heat tracing for protection of fire sprinkler piping in the parging garage and 4th floor. Heat trace panel # 12 not completed - fire sprinkler supply main not installed yet. Also heat trace near pipe to FDC connection not completed. Contractor to call for re-inspection when these items are addressed. Otherwise heat tracing interface with FACP for supervisory alarms for loss of power to unit, and unit troubles tested OK.