ELE16-03319
| Conference | 10/18/2016 | 10/19/2016 | 10/19/2016 1:29:17 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Kendra Lanham Rescheduled for next day, Contactor not available until late in afternoon and will not be in area rest of day. Thank you
|
ELE15-00495
| Final | 10/18/2016 | 10/19/2016 | 10/19/2016 11:35:54 AM | A | NR |
|
|
Reinspect items needed completion for final of Core and Shell. Contact is Toby Groves ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves Mandatory for final- Repair firewall 7th floor ELE rm rt of door. Arc flash warnings on all electrical equipment. Other items cans be covered by new permit mostly cosmetic issues. 4th fl. ELE rm shall not be used for storage. 1st fl. cable tray bond need to terminate at tray. VRT ramp light trims needed 6. VRT fuse down 2 480 volt AC units. VRT, 2nd, 3rd floor parking garages complete heat trace installation. 1st floor GBAD future TI shall support blue MC. 1st floor GBAD shall include fire riser metal underground water pipe for grounding electrode system. 3rd fl. GBAD BSU future TI box required for MC in ceiling near door. RTU-1 service receptacle had open neutral. Walkway up lighting and inground drivers listing or field evaluate. Some existing step light covers needed and junctions need attention. Broken PVC connectors N. E. far corner.
|
ELE16-03390
| Final | 10/18/2016 | 10/19/2016 | 10/19/2016 8:47:50 AM | A | CANC |
|
|
Toby Groves is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Needed temp service inspection
|
ELE16-03390
| Temporary Service | 10/19/2016 | 10/19/2016 | 10/19/2016 8:47:17 AM | P | FAIL |
|
|
Toby Groves is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce 110.26- Minimum work space shall be provided for temp service. 30" wide and 36" deep in front of service. 590.6(B)- Receptacles other than 125 volt shall have GFCI protection if used for construction.
|