Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03065 Final10/19/201610/19/201610/19/2016 1:23:06 PMPNR
Phone #: ###-#### Inspection requested via web by Kurt Carlson
Not ready, discussed all LV boxes shall be closed for electrical final. Also discussed no GFCI protection for sump pump under sink nor Micro, not considered a kitchen since there is no 240v recept installed
ELE16-02600 Electrical Rough-In10/18/201610/19/201610/19/2016 12:25:28 PMAPASS
Dave. Phone #: ###-#### Inspection requested via web by Sean DeLacy
6th floor hard lids and 4th floor rooms as noted ok cover
ELE16-03144 Final10/18/201610/19/201610/19/2016 10:55:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Louis Keller
Final ok
ELE13-00256 Final10/18/201610/19/201610/19/2016 10:45:51 AMAFAIL
Ryan-call for access Phone #: ###-####
210.8 GFCI shall be located in readily accessible location (gate will be changed to swing opposite direction so it wont hit meter)
ELE16-03023 Final10/19/201610/19/201610/19/2016 10:26:58 AMAFAIL
Partial final Phone #: ###-#### Inspection requested via web by Bud Medcoff
210.8 all 120v receptacles in a commercial kitchen shall have GFCI protection
408.4 Field Identification
required
760.121(b) Fire alarm circuit shall be labeled in red indification letters or mark OCPD
(contractor stated all exterior soffit lights will be removed)
ELE15-03995 Final10/17/201610/19/201610/19/2016 9:57:45 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Sign final ok