FIR15-00382
| INSP-Conference | 10/11/2017 | 10/16/2017 | | A | |
|
|
Follow up with Colton
|
BLD17-00617
| FIRE-Final Inspection | 10/19/2017 | 10/19/2017 | 10/19/2017 2:14:35 PM | A | PASS |
|
|
Life safety passed
Phone #: ###-#### Inspection requested via web by kevin debelloy
|
FIR17-00555
| INSP-Final Inspection | 10/18/2017 | 10/19/2017 | 10/19/2017 1:56:18 PM | P | FAIL |
|
|
Provide 24 hour back up power as per the review comments for the internet form of communication, relocate the smoke detector to be above the facp, provide the shield wire between the AES and facp, remove the horn/strobe from the lobby, provide as-builts showing the two low air and to water flow switches, provide functional testing of the two low air and two water flow switches, provide document box, provide updated map
Peter - new fire alarm panel Phone #: ###-####
|
BLD17-00525
| FIRE-Final Inspection | 10/18/2017 | 10/19/2017 | 10/19/2017 11:11:46 AM | A | PASS |
|
|
Life safety passed.
Matthew Phone #: ###-####
|
BLD17-03582
| FIRE-Final Inspection | 10/18/2017 | 10/19/2017 | 10/19/2017 8:58:10 AM | A | PASS |
|
|
Life safety passed
Bridgette Phone #: ###-####
|
FIR16-00284
| INSP-Sprinkler Rough-in/Hydro | 10/18/2017 | 10/19/2017 | 10/19/2017 8:49:23 AM | A | DONE |
|
|
24 hour air test on dry system started at 8:45 with 44psi on the guage.
|
FIR16-00446
| INSP-Alarm Testing | 10/18/2017 | 10/19/2017 | 10/19/2017 8:38:28 AM | A | DONE |
|
|
For todays inspection I witnessed the corrections for the notification devices and verified sync. and that all notification devices were functional. No initiating devices have been tested. Not all access has been provided for the fire/smoke dampers and not all of the fire sprinkler devices have been connected and pre-tested yet.
|
FIR17-00570
| INSP-Final Inspection | 10/18/2017 | 10/19/2017 | 10/19/2017 8:36:23 AM | A | FAIL |
|
|
Strobe modifications are needed due to the new mechanical closet blocking coverage.
|
FIR17-00539
| INSP-Final Inspection | 10/18/2017 | 10/19/2017 | 10/19/2017 8:35:33 AM | A | PASS |
|
|
Permit finaled
|