FIR17-00363
| INSP-Sprinkler Rough-in | 10/19/2017 | 10/19/2017 | 10/19/2017 2:41:00 PM | P | PASS |
|
|
Rough to cover inspection for remaining overhead fire sprinkler piping complete, approved for cover.
|
FIR17-00267
| INSP-Sprinkler Rough-in | 10/19/2017 | 10/19/2017 | 10/19/2017 2:40:02 PM | P | PART |
|
|
Rough to cover for overhead fire sprinkler piping on southside of level 4 complete as well as northside level 4 east of the elevator lobby, areas inspected are approved for cover.
|
FIR17-00550
| INSP-Sprinkler Rough-in | 10/19/2017 | 10/19/2017 | 10/19/2017 1:39:53 PM | P | PASS |
|
|
Rough to cover inspection for area of work complete, area of work approved for cover.
|
FIR16-00267
| INSP-Sprinkler Rough-in/Hydro | 10/19/2017 | 10/19/2017 | 10/19/2017 1:13:29 PM | P | PART |
|
|
Hydrostatic test for level 3 complete. Rough to ocver inspection for remaining pipe on level 3 complete, approved for cover.
|
FIR17-00501
| INSP-Sprinkler Rough-in | 10/18/2017 | 10/19/2017 | 10/19/2017 11:40:09 AM | A | PASS |
|
|
Rough to cover inspection for remaining underground supply complete, approved for cover.
|
FIR17-00473
| INSP-Sprinkler Rough-in | 10/18/2017 | 10/19/2017 | 10/19/2017 11:21:39 AM | A | PART |
|
|
Partial rough to cover inspection complete for level 2, notated the city approved drawings with yellow highlighter/red ink areas approved for cover.
|
BLD17-02336
| FIRE-Final Inspection | 10/18/2017 | 10/19/2017 | 10/19/2017 11:01:48 AM | A | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR17-00428
| INSP-Final Inspection | 10/19/2017 | 10/19/2017 | 10/19/2017 11:00:42 AM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR17-00317
| INSP-Sprinkler Rough-in | 10/18/2017 | 10/19/2017 | 10/19/2017 10:17:05 AM | A | PART |
|
|
Partial rough to ocver inspection complete, notated the city approved drawings with yellow highlighter/red ink area's approved for cover.
|
FIR17-00604
| INSP-Conference | 10/18/2017 | 10/19/2017 | 10/19/2017 10:16:04 AM | A | DONE |
|
|
Fire conference complete, pull station will be mounted in discussed location near the handwash sink.
|