Inspections for the day of: Wednesday, October 2, 2002.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-03035 Rough-In Permanent Service10/1/200210/2/200210/2/2002 12:00:00 AMAFAIL
###-#### cor. posted called 334.30 romex stapled on edge, 314.20 boxes set at 1/4 inch or less should be set 1/2 inch 110.3(B) too many cables under one staple 10/2/2002 12:05:10 PM
ELE02-02466 Final10/1/200210/2/200210/2/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 10/01/2002 at 14:59:45. Contact: ###-####.ok 10/2/2002 11:11:18 AM
ELE02-02914 Electrical Rough-In10/1/200210/2/200210/2/2002 12:00:00 AMAPART
jess; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie u/g south half of building 10/2/2002 10:43:59 AM
ELE02-02675 Final10/2/200210/2/200210/2/2002 12:00:00 AMAPASS
ok
ELE02-03012 Electrical Rough-In10/2/200210/2/200210/2/2002 12:00:00 AMPFAIL
###-#### cor. posted met with owner UAC 301.1,and 305.1 shall uncover all u/g installed without permit,and required inspections 250.52(A)(3) shall install concrete encased elctrode and call for inspectins before cover, 33.30and 314.17(C) staple romex within 8 or 12 inches of boxes, 110.3(B) shall use only listed PVC electrical fittings, BCC shall have all makeup done before inspection requested 10/2/2002 4:35:11 PM
ELE98-00650 Final10/2/200210/2/200210/2/2002 12:00:00 AMPNR
DENNIS ###-#### needs to sheetrock, or rewire,or protect cable 10/2/2002 5:04:56 PM
ELE02-02052 Final10/2/200210/2/200210/2/2002 12:00:00 AMPFAIL
###-#### kevin gfci needed for upstairs bath install all light fixtures, correct, hot grd reversed at recepts hall and family rm met with contractor 10/2/2002 3:12:15 PM
ELE02-01546 Final10/2/200210/2/200210/2/2002 12:00:00 AMPFAIL
duplex 0973 0974 garage codes; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung cor. posted called left message 110.26(F)(2) remove phone equip from below p/s, 314.16 box size end of counter both units, 110.3 (B)and 300.10 shall not use steel flex at non metallic boxes or alter boxes both units 210.8(A)(6)and 210.52(B&C)all outlets that serve kit. counter shall have gfci, and be on small appliance branch circuit counter desk in dinning rm 10/2/2002 5:49:34 PM
ELE02-01742 Final10/2/200210/2/200210/2/2002 12:00:00 AMPPASS
duplex 0975 0976garage code; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok both units 10/2/2002 5:38:36 PM