BLD02-02104
| FIRE-Final Inspection | 10/1/2002 | 10/2/2002 | 10/2/2002 12:00:00 AM | A | PASS |
|
|
fire life/safety finaled. One fire extinguisher needed to be tagged but the owners representative, named Lee called Grinnell and they are to be right out to tag the extinguisher 10/2/2002 9:02:58 AM
|
BLD02-00700
| FIRE-Final Inspection | 10/1/2002 | 10/2/2002 | 10/2/2002 12:00:00 AM | A | PASS |
|
|
fire life/safety finaled 10/2/2002 11:06:23 AM
|
FIR02-00354
| INSP-Final Inspection | 10/1/2002 | 10/2/2002 | 10/2/2002 12:00:00 AM | A | FAIL |
|
|
sprinkler pendant at front entrance is being blocked by the exit sign, the new and existing sprinkler hangers are mounted on the bottom chord of the trusses. This is not per code. All hangers to be attached to the top chord and to be provided with retaining straps 10/2/2002 2:00:31 PM
|
FIR02-00296
| INSP-Final Inspection | 10/2/2002 | 10/2/2002 | 10/2/2002 12:00:00 AM | P | PASS |
|
|
fire sprinkler system finaled 10/2/2002 3:43:06 PM
|