Inspections for the day of: Wednesday, October 2, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-02104 FIRE-Final Inspection10/1/200210/2/200210/2/2002 12:00:00 AMAPASS
fire life/safety finaled. One fire extinguisher needed to be tagged but the owners representative, named Lee called Grinnell and they are to be right out to tag the extinguisher 10/2/2002 9:02:58 AM
BLD02-00700 FIRE-Final Inspection10/1/200210/2/200210/2/2002 12:00:00 AMAPASS
fire life/safety finaled 10/2/2002 11:06:23 AM
FIR02-00354 INSP-Final Inspection10/1/200210/2/200210/2/2002 12:00:00 AMAFAIL
sprinkler pendant at front entrance is being blocked by the exit sign, the new and existing sprinkler hangers are mounted on the bottom chord of the trusses. This is not per code. All hangers to be attached to the top chord and to be provided with retaining straps 10/2/2002 2:00:31 PM
FIR02-00296 INSP-Final Inspection10/2/200210/2/200210/2/2002 12:00:00 AMPPASS
fire sprinkler system finaled 10/2/2002 3:43:06 PM