ELE03-01751
| Electrical Rough-In | 10/2/2003 | 10/2/2003 | 10/2/2003 10:37:22 AM | P | CANC |
|
|
Cover inspection on five rooms in North wing.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs Inspection cancelled from web by: Kathy Briggs
|
ELE03-00245
| Final | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | | FAIL |
|
|
###-#### TOM cor. posted called grd or bond, and install n2 grd rods for p/s at pump house, needs neutral to p/s 250.24(B),, 300.4, 356.30 &348.30 strap sealtight and flex 10/2/2003 10:13:32 AM
|
ELE03-02803
| Final | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok no card 10/2/2003 8:08:33 AM
|
ELE03-03065
| Rough-In Permanent Service | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Annette Moore r/i ok
p/s u/g new ok 10/2/2003 8:52:40 AM
|
ELE03-00057
| Final | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/2/2003 at 7:13:04 AM. Contact: ###-####. temp occupancy ok 10/2/2003 3:49:50 PM
|
ELE03-02300
| Final | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 10/2/2003 at 7:14:00 AM. Contact: ###-####. ok survey posted 10/2/2003 11:10:38 AM
|
ELE03-03067
| Rough-In Permanent Service | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | FAIL |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
cor. posted called needs #10 feed and 30 amp for W H, 230.24(A) 8 ft over roof 10/2/2003 9:54:37 AM
|
ELE03-03056
| Final | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
###-#### joe ok no card 10/2/2003 8:09:09 AM
|
ELE03-03055
| Final | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
###-#### joe ok no card 10/2/2003 8:08:10 AM
|
ELE03-01947
| Final | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | PASS |
|
|
ok
|
ELE03-03080
| Temporary Service | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | PASS |
|
|
###-#### george t/s u/g new ok 10/2/2003 2:28:46 PM
|
ELE03-02909
| Electrical Rough-In | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | PASS |
|
|
skip ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 10/2/2003 1:06:15 PM
|
ELE03-03066
| Electrical Rough-In | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | FAIL |
|
|
###-#### clay meter base inspect only
cor. posted called needs 2" mast with required clearence, no open wiring in wall, clearence for panel old p/s now sub panel check range and dryer feeds, bring all grounding up to 2002 NEC 10/2/2003 1:43:00 PM
|