FIR03-00364
| FIR-Aging Inspection | 10/2/2003 | 10/2/2003 | 10/7/2003 12:00:00 AM | | PASS |
|
|
wip 10/7/2003 1:01:15 PM
|
FIR03-00303
| FIR-Aging Inspection | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | | PASS |
|
|
wip 10/2/2003 7:27:13 AM
|
BLD02-00090
| FIRE-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PART |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie per Dave Miller fire/life safety will be on temp occupancy until the access control system is tested and disables with fire alarm activation and approval of the pressure reducing valve is submitted and approved by plan review 10/2/2003 9:14:25 AM
|
FIR03-00068
| INSP-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PART |
|
|
as per requestd, to test peration of pressure relief valve.; Phone #: ###-#### Internet Inspection Request from: Trent Bice 10/2/2003 9:12:44 AM pressure-reducing valve is installed; need submittals to plan review and approval prior to final sign-off 10/2/2003 2:54:29 PM
|
BLD02-01073
| FIRE-Final Inspection | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 10/2/2003 at 7:30:50 AM. Contact: ###-####. will have restroom/office and playroom door hardware openable from the inside without special knowledge for structural inspection; right now the levers don't release the lock 10/2/2003 10:55:21 AM
|
MIS03-00167
| FIR-Final | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
###-#### richard
|
FIR03-00216
| INSP-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
This is Bobs # from Lea Electric; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
FIR03-00276
| INSP-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
This is Bobs # from Lea Electric; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
FIR03-00267
| INSP-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PASS |
|
|
This is Bobs # from Lea Electric; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
FIR03-00375
| INSP-Sprinkler Rough-in/Hydro | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/1/2003 at 2:01:10 PM. area on first floor okay to cover except by the NE area by stair as SSU and SSP are too close together - reinspection needed to cover this area; sidewall installed under stair instead of pendant as shown on plans 10/2/2003 9:52:07 AM
|
BLD02-02435
| FIRE-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | A | FAIL |
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Darla Downs need"Fire lane no parking" on red curbing; page 2 of sprinkler certificates 10/2/2003 11:20:17 AM
|
BLD03-01833
| FIRE-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/1/2003 at 3:48:53 PM. Contact: ###-####.
|
BLD03-01833
| FIRE-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 10/1/2003 at 3:48:53 PM. Contact: ###-####. received a call from Jeff and they aren't ready and will reschedule 10/2/2003 1:49:35 PM
|
FIR02-00311
| INSP-Final Inspection | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | PASS |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Darla Downs all items completed 10/2/2003 1:20:54 PM
|
BLD02-01217
| FIRE-Final Inspection | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | FAIL |
|
|
don ; Phone #: ###-#### Internet Inspection Request from: Annette Moore need fire extinguisher per instructions on correction notice 10/2/2003 3:25:59 PM
|
FIR03-00550
| INSP-Final Inspection | 10/2/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | PART |
|
|
pat ###-#### will need map with zones at annunciator; will complete testing after the rest of the RTU's are installed; tested RTU's in toy store and everton only; sprinkler system tested for flow and tampers 10/2/2003 5:08:57 PM
|
FIR03-00308
| INSP-Alarm Testing | 9/29/2003 | 10/2/2003 | 10/2/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/29/2003 at 11:59:37 AM. Contact: ###-####.
|