ELE05-04325
| Electrical Rough-In | 10/2/2006 | 10/2/2006 | 10/2/2006 3:55:09 PM | P | PASS |
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 2nd anop
|
ELE06-02657
| Electrical Rough-In | 10/2/2006 | 10/2/2006 | 10/2/2006 2:57:37 PM | P | PART |
|
|
loren; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls and hard ceilings east west back half
|
ELE06-03477
| Final | 10/2/2006 | 10/2/2006 | 10/2/2006 2:01:39 PM | P | PASS |
|
|
kathy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE06-03534
| Rough-In Permanent Service | 10/2/2006 | 10/2/2006 | 10/2/2006 1:37:09 PM | P | FAIL |
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called outside of house ok for cover only, 210.52(A) required outlets 2 in din rm 1 in liv rm, 300.14 grds cut short, 250.148 grd all metal boxes, 230.6 no service entrance conductors allowed in wall (SER) cable, 230.24 needs 8ft clearence from drip loop to roof
|
ELE06-03504
| Rough-In Permanent Service | 10/2/2006 | 10/2/2006 | 10/2/2006 12:30:30 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/2/2006 at 7:01:35 AM. Contact: ###-####. r/i p/s u/g new ok
|
ELE06-03503
| Rough-In Permanent Service | 10/2/2006 | 10/2/2006 | 10/2/2006 12:30:03 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/2/2006 at 7:00:48 AM. Contact: ###-####. r/i p/s u/g new ok
|
ELE05-04401
| ELE-Aging Inspection | 10/2/2006 | 10/2/2006 | 10/2/2006 10:30:48 AM | | PART |
|
|
called
|
ELE05-04431
| ELE-Aging Inspection | 10/2/2006 | 10/2/2006 | 10/2/2006 10:28:14 AM | | DONE |
|
|
|
ELE05-04431
| Final | 10/2/2006 | 10/2/2006 | 10/2/2006 10:28:04 AM | A | PASS |
|
|
|
ELE06-03009
| Electrical Rough-In | 9/29/2006 | 10/2/2006 | 10/2/2006 10:12:21 AM | A | PASS |
|
|
robert - call prior to insp (homeowner); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
|
ELE06-00976
| Electrical Rough-In | 9/29/2006 | 10/2/2006 | 10/2/2006 9:28:21 AM | A | FAIL |
|
|
Alan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. called, 110.3(A) replace damaged romex, 300.4(D) 11/4" from edges, 300.16 box fill, complete all makeup , provide 6" free length COW
|
ELE06-03324
| Final | 9/29/2006 | 10/2/2006 | 10/2/2006 8:57:24 AM | A | FAIL |
|
|
rod; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley no access left message
|
ELE06-03404
| Electrical Rough-In | 9/29/2006 | 10/2/2006 | 10/2/2006 8:38:14 AM | A | PART |
|
|
underground conduit; Phone #: ###-#### Internet Inspection Request from: Celinda Winters u/g ok
|
ELE06-03534
| Rough-In Permanent Service | 9/29/2006 | 10/2/2006 | 10/2/2006 8:06:16 AM | A | CANC |
|
|
chad - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr canceled
|
ELE06-03649
| Electrical Rough-In | 10/1/2006 | 10/2/2006 | 10/1/2006 1:43:29 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/1/2006 at 9:37:36 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Oct 1 2006 1:43PM.
|
ELE06-03551
| Final | 9/26/2006 | 10/2/2006 | 9/29/2006 8:59:44 AM | P | CANC |
|
|
Kitchen remodel:1)installed 5 new recessed can lights on existing switching,2)relocated the existing oven circuit and receptacle,3)relocated the existing frig circuit and receptacle,4)relocated the existing dishwasher circuit and receptacle,5)replaced all kitchen receptacles and switches,6)wired a new receptacle on the existing circuit for microwave,7)wired a new receptacle on existing circuit for the new Appliance garage,8)wired a new receptacle on the existing circuit for the telephone station.(6080905r)Tech/Jason/###-####.Thanks!!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell Inspection cancelled from web by: Cathy Weisshaupt
|