ELE06-03481
| Electrical Rough-In | 10/2/2006 | 10/2/2006 | 10/11/2006 12:00:00 AM | P | DONE |
|
|
Jerod, please call when you arrive, he''''s next door; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt due wrong permit
|
ELE06-01173
| Final | 10/2/2006 | 10/2/2006 | 10/2/2006 4:38:44 PM | P | PASS |
|
|
Internet Inspection Request from: Rowdy Monroe ok to final
|
ELE06-00117
| Final | 10/2/2006 | 10/2/2006 | 10/2/2006 4:05:04 PM | P | PART |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for showroom area only, signed card, left corr notice, nec 514.3(B)(1) fuel dispenser shall provide clearances per table, 511.12 recpts shall be gfci, 511.3(A)(5) wiring shall be 18" above floor or class1, 430.102(B) door opener shall have disconnect, 330.39(B) mc cable shall be secured within 12" of box, BCC 4-05-33(A)&(B) exhaust system shall listed and labelled , check polarity on lifts and complete soffit lighting,NOTE: corrections shall be made in 2 weeks or further action can be taken such as removal of power
|
ELE06-02598
| Final | 10/2/2006 | 10/2/2006 | 10/2/2006 3:47:33 PM | P | PASS |
|
|
andy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
ELE06-03668
| Electrical Rough-In | 10/2/2006 | 10/2/2006 | 10/2/2006 2:39:27 PM | P | PART |
|
|
###-#### - jerod u/g in slab ok, gec was ok'd under t/s permit, was supposed to be finalled,
|
ELE06-03206
| Electrical Rough-In | 10/2/2006 | 10/2/2006 | 10/2/2006 2:28:59 PM | P | PASS |
|
|
stu Note: ceiling ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles clg ok to cover
|
ELE06-03098
| Electrical Rough-In | 10/2/2006 | 10/2/2006 | 10/2/2006 2:01:57 PM | P | PASS |
|
|
jeremy Note: ufier; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, ok to cover gec, told no more inspections without address posted
|
ELE06-03652
| Final | 9/29/2006 | 10/2/2006 | 10/2/2006 11:41:37 AM | A | PASS |
|
|
Jay; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
|
ELE06-03648
| Electrical Rough-In | 9/29/2006 | 10/2/2006 | 10/2/2006 10:14:49 AM | A | PASS |
|
|
jeanna; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok
|
ELE06-03651
| Permanent Service | 9/29/2006 | 10/2/2006 | 10/2/2006 9:40:53 AM | A | PASS |
|
|
need perm service inspection on 200 amp service, mobile home hook up. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH p/s u/g exst rec ok
|
ELE06-03569
| Electrical Rough-In | 10/1/2006 | 10/2/2006 | 10/2/2006 9:23:43 AM | A | PASS |
|
|
grounding grid inspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman ok to pour equi-pot grid
|
ELE06-00113
| Final | 9/29/2006 | 10/2/2006 | 10/2/2006 8:44:38 AM | A | PART |
|
|
Greg, partial for 10th floor only, please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt rooms and ceilings anop ok
|