ELE07-01624
| Electrical Rough-In | 10/2/2007 | 10/2/2007 | 10/2/2007 3:32:04 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/2/2007 at 7:21:04 AM. Contact: ###-####. walls only parts of 1st and second floors anop ok to cover
|
ELE07-01269
| Final | 10/2/2007 | 10/2/2007 | 10/2/2007 2:55:33 PM | P | PASS |
|
|
ok to final
|
ELE07-03130
| Conference | 10/2/2007 | 10/2/2007 | 10/2/2007 2:54:02 PM | P | DONE |
|
|
CASEY Phone #: ###-#### talked about new addition, outlet spacing, afci breakers, when to come for ri inspection
|
ELE06-02298
| Rough-In Permanent Service | 10/1/2007 | 10/2/2007 | 10/2/2007 2:29:06 PM | P | PASS |
|
|
marv - please call 1/2 hr prior to inspection Phone #: ###-#### ri ok for service areas only, will doe areas of ri for house later, p/s u/g n ok
|
ELE07-03375
| Electrical Rough-In | 10/2/2007 | 10/2/2007 | 10/2/2007 1:09:39 PM | P | PASS |
|
|
trent Phone #: ###-#### walls only ok to cover
|
ELE07-03374
| Electrical Rough-In | 10/2/2007 | 10/2/2007 | 10/2/2007 12:55:35 PM | P | PASS |
|
|
trent Phone #: ###-#### walls only ok to cover
|
ELE07-03371
| Rough-In Permanent Service | 10/1/2007 | 10/2/2007 | 10/2/2007 10:58:12 AM | A | CANC |
|
|
please call prior to inspection so I can meet you there and explain whats going on thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker see ri and p/s
|
ELE07-03371
| Permanent Service | 10/2/2007 | 10/2/2007 | 10/2/2007 10:53:08 AM | A | PASS |
|
|
please call prior to inspection so I can meet you there and explain whats going on thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker talked with contr, p/s o/h n ok
|
ELE07-03371
| Electrical Rough-In | 10/2/2007 | 10/2/2007 | 10/2/2007 10:52:11 AM | A | NR |
|
|
please call prior to inspection so I can meet you there and explain whats going on thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker talked with contractor, will do ri later
|
ELE07-03355
| Final | 10/2/2007 | 10/2/2007 | 10/2/2007 10:37:12 AM | A | PASS |
|
|
p/s u/g n ok
|
ELE07-03393
| Electrical Rough-In | 10/1/2007 | 10/2/2007 | 10/2/2007 10:21:23 AM | A | NR |
|
|
UFFER inspection. Phone #: ###-#### Internet Inspection Request from: Todd Sellman called contr, no steel yet, will recall
|
ELE07-02620
| Final | 10/2/2007 | 10/2/2007 | 10/2/2007 10:10:54 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, ok to final
|
ELE07-02737
| Final | 10/2/2007 | 10/2/2007 | 10/2/2007 9:36:25 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus called contr, ok to final, signed occ card
|
ELE07-03248
| Permanent Service | 10/1/2007 | 10/2/2007 | 10/2/2007 8:59:54 AM | A | FAIL |
|
|
richard Note: please call 30 min to get in Phone #: ###-#### met contr, told correction required 2 ground rods per nec 250.53 (D)(2), will call later after correction made, rest of service ok
|
ELE07-03394
| Electrical Rough-In | 10/1/2007 | 10/2/2007 | 10/2/2007 8:37:18 AM | A | FAIL |
|
|
george Phone #: ###-#### called, left corr notice, nec 300.4(A) & (D) edge of bored holes, mc cable and ent shall be 1 1/4" from edge of framing members, BCC raceways shall not be run in valley of framing members
|
ELE07-03392
| Electrical Rough-In | 10/1/2007 | 10/2/2007 | 10/2/2007 8:20:15 AM | A | PASS |
|
|
Rough in on exterior soffit ###-#### Internet Inspection Request from: Todd Holbrook ok to cover soffits only
|