Inspections for the day of: Thursday, October 2, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00296 Electrical Rough-In10/2/200810/2/200810/2/2008 4:11:03 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Karl Paige called will do in AM contr leaves at 3:45PM called
ELE08-02665 Permanent Service10/2/200810/2/200810/2/2008 4:08:45 PMPFAIL
kevin Phone #: ###-#### called corr/ 230.9(A) mast shall be 3ft from window,310.8(D) needs sun-res wire for mast
ELE08-02679 Electrical Rough-In10/1/200810/2/200810/2/2008 2:52:31 PMPFAIL
Brian Phone #: ###-#### called box fill oulet spacing countertop kit. by pocket door, address the 2 SABC and micro wave and DW , disposal circuits corr posted

also correction posted for alloway elect for work they did back in 1998 per # ele98-01700 called
ELE08-02683 Permanent Service10/2/200810/2/200810/2/2008 1:46:09 PMPPASS
Steve- call 30 min prior Phone #: ###-####
p/s u/g rec. ok
ELE08-02683 Final10/2/200810/2/200810/2/2008 1:45:45 PMPPASS
Steve- call 30 min prior Phone #: ###-####
ELE08-01787 Electrical Rough-In10/2/200810/2/200810/2/2008 12:58:19 PMAPART
Scheduled by a contractor via Hello! on 10/2/2008 at 7:06:11 AM. Contact: ###-####. 3 outlet in deli ok
ESC08-00665 General Inspection10/2/200810/2/200810/2/2008 12:06:06 PMAPART
ok
ELE08-02671 Electrical Rough-In10/1/200810/2/200810/2/2008 12:05:06 PMAFAIL
Lars Phone #: ###-#### called job not ready and corrections, 300.4 nail plates, 334.23 protect cables at both attic accesses, 210.11(C)(2) all recepts in laundry rm shall be on laundry circuit, 406.8(C) outlet not allowed over tub enclosure, install and complete makeup for outside boxes, and terminate 14/2 cable into box in closet
ESC08-00459 General Inspection10/2/200810/2/200810/2/2008 10:21:43 AMAPART
ELE08-02588 Rough-In Permanent Service10/1/200810/2/200810/2/2008 10:21:08 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Stephen Kren r/i p/s u/g new ok
ELE08-01923 Final10/1/200810/2/200810/2/2008 9:33:14 AMAPART
ernie Phone #: ###-#### needs to address bonding of roof , and window metal for spa
called people can move in to house. JMS
ELE08-02490 Electrical Rough-In10/1/200810/2/200810/2/2008 9:31:55 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson r/i ok still needs concrete encased electrodeor find rebar in foundation see notes p/s request
ELE08-02586 Final10/1/200810/2/200810/2/2008 8:24:45 AMAPASS
luke Phone #: ###-#### ok no card