ELE08-00296
| Electrical Rough-In | 10/2/2008 | 10/2/2008 | 10/2/2008 4:11:03 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Karl Paige called will do in AM contr leaves at 3:45PM called
|
ELE08-02665
| Permanent Service | 10/2/2008 | 10/2/2008 | 10/2/2008 4:08:45 PM | P | FAIL |
|
|
kevin Phone #: ###-#### called corr/ 230.9(A) mast shall be 3ft from window,310.8(D) needs sun-res wire for mast
|
ELE08-02679
| Electrical Rough-In | 10/1/2008 | 10/2/2008 | 10/2/2008 2:52:31 PM | P | FAIL |
|
|
Brian Phone #: ###-#### called box fill oulet spacing countertop kit. by pocket door, address the 2 SABC and micro wave and DW , disposal circuits corr posted
also correction posted for alloway elect for work they did back in 1998 per # ele98-01700 called
|
ELE08-02683
| Permanent Service | 10/2/2008 | 10/2/2008 | 10/2/2008 1:46:09 PM | P | PASS |
|
|
Steve- call 30 min prior Phone #: ###-#### p/s u/g rec. ok
|
ELE08-02683
| Final | 10/2/2008 | 10/2/2008 | 10/2/2008 1:45:45 PM | P | PASS |
|
|
Steve- call 30 min prior Phone #: ###-####
|
ELE08-01787
| Electrical Rough-In | 10/2/2008 | 10/2/2008 | 10/2/2008 12:58:19 PM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/2/2008 at 7:06:11 AM. Contact: ###-####. 3 outlet in deli ok
|
ESC08-00665
| General Inspection | 10/2/2008 | 10/2/2008 | 10/2/2008 12:06:06 PM | A | PART |
|
|
ok
|
ELE08-02671
| Electrical Rough-In | 10/1/2008 | 10/2/2008 | 10/2/2008 12:05:06 PM | A | FAIL |
|
|
Lars Phone #: ###-#### called job not ready and corrections, 300.4 nail plates, 334.23 protect cables at both attic accesses, 210.11(C)(2) all recepts in laundry rm shall be on laundry circuit, 406.8(C) outlet not allowed over tub enclosure, install and complete makeup for outside boxes, and terminate 14/2 cable into box in closet
|
ESC08-00459
| General Inspection | 10/2/2008 | 10/2/2008 | 10/2/2008 10:21:43 AM | A | PART |
|
|
|
ELE08-02588
| Rough-In Permanent Service | 10/1/2008 | 10/2/2008 | 10/2/2008 10:21:08 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Stephen Kren r/i p/s u/g new ok
|
ELE08-01923
| Final | 10/1/2008 | 10/2/2008 | 10/2/2008 9:33:14 AM | A | PART |
|
|
ernie Phone #: ###-#### needs to address bonding of roof , and window metal for spa called people can move in to house. JMS
|
ELE08-02490
| Electrical Rough-In | 10/1/2008 | 10/2/2008 | 10/2/2008 9:31:55 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson r/i ok still needs concrete encased electrodeor find rebar in foundation see notes p/s request
|
ELE08-02586
| Final | 10/1/2008 | 10/2/2008 | 10/2/2008 8:24:45 AM | A | PASS |
|
|
luke Phone #: ###-#### ok no card
|