ELE08-02575
| Final | 10/2/2008 | 10/2/2008 | 10/2/2008 4:07:36 PM | P | PASS |
|
|
Please call 20 min prior to arrival Phone #: ###-#### Internet Inspection Request from: John Edwards talked with contractor, ok to final, no esc this project
|
ELE08-01821
| Final | 10/2/2008 | 10/2/2008 | 10/2/2008 3:22:05 PM | A | PASS |
|
|
looked at sign ok to final, no esc this project
|
ESC08-00365
| General Inspection | 10/2/2008 | 10/2/2008 | 10/2/2008 3:20:37 PM | A | PASS |
|
|
looked ok
|
ELE08-02682
| Rough-In Permanent Service | 10/2/2008 | 10/2/2008 | 10/2/2008 3:19:33 PM | P | CANC |
|
|
John Phone #: ###-#### see p/s and ri
|
ELE08-02682
| Electrical Rough-In | 10/2/2008 | 10/2/2008 | 10/2/2008 2:45:08 PM | P | PASS |
|
|
John Phone #: ###-#### ok to cover u/g house to garage, need to do ri for garage, no esc this project
|
ELE08-02682
| Permanent Service | 10/2/2008 | 10/2/2008 | 10/2/2008 2:38:27 PM | P | PASS |
|
|
John Phone #: ###-#### at final check water pipe ground, sub-panel in house and garage, 2 ground rods are installed , check junction box below panel or conduit size, p/s o/h rec ok, no esc this project
|
ELE08-02680
| Rough-In Permanent Service | 10/2/2008 | 10/2/2008 | 10/2/2008 2:25:37 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl called, left correction notice, NEC 250.52(A)(1) shall use incoming water pipe as a grounding electrode, 230.24(A) service conductors shall be 8' above roof surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 shall secure nm cable within 12" of box (sub-panel), 210.52(A)(1) shall space receptacles such that no point along floor line is more than 6' from a receptacle outlet, BCC shall change room count to 15 on permit, no esc this project
|
ELE08-01103
| Electrical Rough-In | 10/2/2008 | 10/2/2008 | 10/2/2008 12:45:35 PM | P | PASS |
|
|
forest Phone #: ###-#### 1st floor east side ok for new fixtures, ceiling clean-up is progressing for electrical and low voltage, saw and retreived sample of non-plenum rated cabling that needs replaced, no esc this project
|
ELE08-02391
| Electrical Rough-In | 10/1/2008 | 10/2/2008 | 10/2/2008 10:36:46 AM | A | FAIL |
|
|
luke Note: cover up Phone #: ###-#### called, left message, left corr notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of faming members, 300.14 shall have 6" free conductor length in boxes, 314.5 shall support nm cable within 8" of boxes, 314.23 boxes shall be rigidly supported, 210.52(D) bath receptacle shall be within 3' of edge of basin, 210.52(A) receptacles shall be installed in wall space over 2", 110.26(F) there shall not be a/c lines in dedicated space over panel,300.5 u/g to post lights shall be minimum 18" deep, BCC shall provide boxes in bath areas, shall change room count to 17 rooms on permit, no esc this project
|
ELE08-02211
| Temporary Service | 10/1/2008 | 10/2/2008 | 10/2/2008 9:54:54 AM | A | PASS |
|
|
dale Phone #: ###-#### t/s u/g n ok, no esc this project
|
ELE08-02658
| Electrical Rough-In | 10/1/2008 | 10/2/2008 | 10/2/2008 9:12:35 AM | A | PASS |
|
|
butch - underground Phone #: ###-#### corrections made, u/g only ok to cover, no esc this project
|
ELE08-00307
| Electrical Rough-In | 10/2/2008 | 10/2/2008 | 10/2/2008 8:35:20 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/2/2008 at 6:41:21 AM. Contact: ###-####. met contractor, left correction notice, BCC no ceiling tile shall be installed prior to inspection, no esc this project
|
ELE08-01956
| Electrical Rough-In | 10/1/2008 | 10/2/2008 | 10/2/2008 8:02:15 AM | A | FAIL |
|
|
Rick Phone #: ###-#### called, left correction notice, NEC 330.30(B) mc cable shall be secured within 12" of termination, BCC all fixtures shall be installed
|