Inspections for the day of: Wednesday, October 2, 2013.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00837 Electrical Rough-In10/2/201310/2/201310/2/2013 4:36:29 PMPPASS
Underground inspection please Late afternoon-Mark Phone #: ###-#### Rough-in ok cover underground, east end of trench, next to Turbo Air hanger.
ELE13-02632 Final10/2/201310/2/201310/2/2013 4:20:59 PMPPASS
job complete, final ok
ELE13-02632 Electrical Rough-In10/2/201310/2/201310/2/2013 3:45:11 PMPPASS
Jason-Inspection of Iris reset end cap on Aisle 11 please Phone #: ###-#### Rough-in ok
ELE12-00813 Permanent Service10/2/201310/2/201310/2/2013 2:55:08 PMPFAIL
Larry Phone #: ###-#### NEC 110.26 working clearance of service panel for personal in shark tank office.
ELE12-01885 Electrical Rough-In10/2/201310/2/201310/2/2013 12:46:31 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Rough-in ok cover under slab floor boxes, 3 locations
ELE13-02653 Electrical Rough-In10/2/201310/2/201310/2/2013 12:30:49 PMPPASS
Cover inspection for HP parking lot. Please call Guy with any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover conduits for pole bases only. Southend, first 5 east/west laterals
ELE13-02449 Electrical Rough-In10/1/201310/2/201310/2/2013 11:01:09 AMAPASS
Mike Phone #: ###-#### Rough-in ok cover first floor/garage
ELE13-02705 Final10/1/201310/2/201310/2/2013 10:21:19 AMAFAIL
Please contact the homeowner Paula, to confirm access. She can be reached at ###-####..Contact Vintage electric at ###-####for any questions about the job.. thank you Phone #: ###-#### >> Inspection requested via web by Robert Nelson Nec 406.3(D)(3) Grounding type receptacles shall not be used if no equipment grounding conductor exsist 406.3(d)(3)(b) unless GFCI protected NEC 408.4 Shall complete panel directory.
ELE13-02727 Final10/2/201310/2/201310/2/2013 9:36:49 AMAPASS
job complete, final ok
ELE13-02727 Electrical Rough-In10/1/201310/2/201310/2/2013 9:34:12 AMAPASS
installed 2 mini-split systems
job complete Phone #: ###-#### >> Inspection requested via web by Stuart Welton rough-in ok
ELE13-01506 Electrical Rough-In10/1/201310/2/201310/2/2013 9:11:45 AMAPASS
Bud on site. Partial ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover ceiling grid Pet scan corridor
ELE13-02653 Electrical Rough-In10/1/201310/2/201310/2/2013 8:37:20 AMAPART
Cover inspection for HP parking lot. Call Guy Thomas with any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in Partial cover trench for service panel stub
ELE11-00412 ELE-Aging Inspection10/2/201310/2/201310/2/2013 6:51:49 AM DONE
job under review
ELE13-02653 Electrical Rough-In10/1/201310/2/201310/1/2013 4:25:26 PMACANC
Cover inspection for HP parking lot. Call Guy Thomas with any questions ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate