Inspections for the day of: Thursday, October 2, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00344 INSP-Sprinkler Rough-in10/1/201410/2/201410/3/2014 7:12:15 AMPPART
Third floor area C wet system piping okayed for ceiling cover. Noted corrections completed.
FIR14-00604 INSP-Sprinkler Rough-in10/1/201410/2/201410/3/2014 7:10:05 AMPPART
Verified corrections and adjustments to the dry system C wing as previously noted- Rough-in inspection completed to the masonry wall. Protection at three covered patios has been changed from DSW to DP fed from dry system.
BLD14-02818 FIRE-Final Inspection10/2/201410/2/201410/2/2014 4:13:12 PMPPASS
Verified previous correction items for completion. Fire life safety passed.
FIR14-00470 INSP-Sprinkler Rough-in10/1/201410/2/201410/2/2014 3:35:54 PMPPART
Overhead work okayed for cover at three restrooms, med gas room, and two soffits with sheetrock lids 1st floor as marked and dated on approved plans. Also discussed FDC location.
FIR14-00565 INSP-Sprinkler Rough-in/Hydro10/1/201410/2/201410/2/2014 3:02:51 PMPPART
UG fire supply line hydrostatic test passed.
FIR14-00378 INSP-Final Inspection10/2/201410/2/201410/2/2014 3:01:59 PMPPASS
Scope of work completed. Inspection passed, permit finaled.
FIR14-00379 INSP-Final Inspection10/1/201410/2/201410/2/2014 1:36:06 PMAPART
Inspection and testing completed satisfactory. Final pending signage per review note #20, label documents cabinet, provide NFPA 72 record of completion forms for signature.
FIR14-00394 INSP-Final Inspection10/1/201410/2/201410/2/2014 1:31:22 PMANR
Matt Phone #: ###-####
BLD14-02817 FIRE-Final Inspection10/1/201410/2/201410/2/2014 12:18:57 PMAPART
Approved for temporary occupancy per conditions of the upgrade agreement on file. Need to post max occupancy signage at 99 near the main entry/exit per plan key note, repair one EM light at the east wall dining area.
BLD14-02818 FIRE-Final Inspection10/1/201410/2/201410/2/2014 12:15:31 PMAFAIL
Correction items include; missing occupant load signage, need to repair two non-functional exit signs/EM lights, missing fire extinguisher with current certification tag. Refer to approved plan key notes 1 & 2 and annotations for details.