BLD17-02481
| FIRE-Final Inspection | 10/2/2017 | 10/2/2017 | 10/2/2017 3:34:19 PM | P | PASS |
|
|
Life safety passed.
Dave Phone #: ###-####
|
BLD17-00335
| FIRE-Final Inspection | 10/2/2017 | 10/2/2017 | 10/2/2017 3:26:57 PM | P | CANC |
|
|
Dave Phone #: ###-####
|
BLD17-00335
| FIRE-Conference | 10/2/2017 | 10/2/2017 | 10/2/2017 3:26:48 PM | P | CANC |
|
|
David Phone #: ###-####
|
NAF17-00037
| INSP-Final | 10/2/2017 | 10/2/2017 | 10/2/2017 3:25:29 PM | P | FAIL |
|
|
All items have been corrected except for the supply piping in the crawl space needs to comply with review note #3.
|
NAF17-00052
| INSP-Alarm Testing | 10/2/2017 | 10/2/2017 | 10/2/2017 3:23:01 PM | P | FAIL |
|
|
Audibles are not sync't, two strobes did not function, no as-builts, delay egress doors are not tied into fire alarm system yet.
|
NAF17-00010
| INSP-Final | 9/29/2017 | 10/2/2017 | 10/2/2017 3:21:24 PM | P | FAIL |
|
|
Life safety will be ok to sign off when the project related fire alarm permit is finaled.
Phone #: 9571618 >> Inspection requested via mobile web by Todd
|
BLD17-01057
| FIRE-Final Inspection | 10/2/2017 | 10/2/2017 | 10/2/2017 1:31:57 PM | P | PASS |
|
|
Life safety passed
|
FIR17-00384
| INSP-Final Inspection | 10/2/2017 | 10/2/2017 | 10/2/2017 1:26:59 PM | P | PASS |
|
|
permit finaled.
|
FIR17-00364
| INSP-Alarm Testing | 10/2/2017 | 10/2/2017 | 10/2/2017 1:23:51 PM | P | PART |
|
|
The fire alarm system/devices for OR 141 passed.
Damon Phone #: ###-####
|
FIR17-00515
| INSP-Final Inspection | 9/29/2017 | 10/2/2017 | 10/2/2017 1:23:11 PM | A | PASS |
|
|
Permit finaled
|
FIR17-00465
| INSP-Final Inspection | 9/29/2017 | 10/2/2017 | 10/2/2017 9:32:38 AM | A | PASS |
|
|
The remaining underground supply piping is ok to cover.
|
BLD17-02363
| FIRE-Final Inspection | 9/29/2017 | 10/2/2017 | 10/2/2017 8:58:18 AM | A | PASS |
|
|
life safety passed
|
FIR17-00572
| INSP-Final Inspection | 10/2/2017 | 10/2/2017 | 10/2/2017 8:57:14 AM | P | PASS |
|
|
permit finaled
|
FIR17-00572
| INSP-Alarm Testing | 9/29/2017 | 10/2/2017 | 10/2/2017 8:56:56 AM | A | PASS |
|
|
Stan Phone #: ###-####
|
FIR17-00566
| INSP-Sprinkler Rough-in | 9/29/2017 | 10/2/2017 | 10/2/2017 8:10:31 AM | A | PART |
|
|
Rough-in passed for the drops. Waiting to T-bar for inspection for arm-overs and ok for cover
|