Inspections for the day of: Tuesday, October 2, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03048 Final10/2/201810/2/201810/2/2018 2:30:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Robert Carter Final ok
ELE18-03607 Electrical Rough-In10/2/201810/2/201810/2/2018 1:59:40 PMPPASS
North canopy Phone #: ###-#### Inspection requested via web by Ron Zimmerman
Rough in ok cover
ELE18-03757 Conference10/2/201810/2/201810/2/2018 1:41:12 PMPPASS
Justin Phone #: ###-####
Discussed 200amp service and overhead clearence of service entrance conductors. Miscommumication with Idaho power on how easy it would be to get around tall shop and refeed house. Roof pitch on shop 3x12 suggested building a stand off on corner of shop and stay below roof to avoid above roof requirements. Has provided a grounding electrode system of ground rods 5'5" apart. Concrete encased electrode is provided on east wall that will be connected when framing complete on that wall. Discussed interior receptacle locations and types and required lights for interior and man doors.
ELE18-03338 Electrical Rough-In10/1/201810/2/201810/2/2018 11:31:37 AMAPASS
Jason Curley ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting
Listing confirmed on roof equipment. Rough in ok
ELE18-03758 Final10/1/201810/2/201810/2/2018 10:54:09 AMAFAIL
Connected whip to A/C unit from disconnect. NOTE: owner installed disconnect and wire. Phone #: ###-#### Inspection requested via web by Kendra Lanham
BCC 04-05-21- Electrical permit required to cover from outdoor panel to HVAC disconnect. Owner stated he provided conduit and wire and electrical contractor terminated wiring. Either owner pulls permit for feed to disconnect or contractor takes responcibility for entire branch circuit.

110.14- Grounding terminations in panel, up to 3 under each termination, but shall be of same size conductor.
110.26- HVAC fused disconnect shall have minimum work space provided 30" wide and 36" deep. Now located behind HVAC unit.
ELE18-03666 Permanent Service10/1/201810/2/201810/2/2018 10:09:39 AMAPASS
Inspector requested mast to be elevated for clearance over parking area. Need a pass for coordination with Idaho Power Phone #: ###-#### Inspection requested via web by Kendra Lanham p/s o/h rec ok
ELE18-03667 Final10/1/201810/2/201810/2/2018 9:51:46 AMAPASS
Please call Micah Hornback at ###-#### so that I can have someone meet you on site for this inspection. Thank you! Phone #: ###-#### Inspection requested via web by Jesse Simpson Final ok
ELE18-03388 Electrical Rough-In10/1/201810/2/201810/2/2018 9:26:02 AMAPASS
Wall cover for kitchen and entertainment room. Greg ###-####. Thank you Phone #: ###-#### Inspection requested via web by Steve Blackmer
Kitchen, bathrooms, family rm rough in ok cover.
ELE18-00849 Electrical Rough-In10/1/201810/2/201810/2/2018 8:45:47 AMAPART
Roger ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Roger not contact Bob is @ ###-####
300.4- Cables shall not be installed with in 1 1/2" of corregated roof. S.W offices and corridor.
N.W. offices level 2 grid rough in ok cover.