Inspections for the day of: Tuesday, October 2, 2018.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03648 Final10/1/201810/2/201810/2/2018 2:08:06 PMPPASS
call 1/2 hr before to meet // kevin Phone #: ###-#### Ok final. Panel labeled.
ELE18-00822 Electrical Rough-In10/2/201810/2/201810/2/2018 1:49:01 PMPPASS
Hi, requesting electrical rough in inspection. I''m at the house all day today. Thanks, Austin Phone #: ###-#### Inspection requested via web by Lauren Perreault Ok cover kitchen area.
ELE18-03648 Permanent Service10/1/201810/2/201810/2/2018 1:21:29 PMPCANC
call 1/2 hr before to meet // kevin Phone #: ###-#### No permanent service. This is just a new sub panel replacing existing.
ELE18-02640 Final10/2/201810/2/201810/2/2018 1:20:30 PMPPASS
Phone #: ###-#### Inspection requested via web by cris flores Ok final.
ELE18-02640 Final10/2/201810/2/201810/2/2018 1:20:14 PMPCANC
Phone #: ###-#### Inspection requested via web by cris flores Duplicate inspection.
ELE18-03461 Final10/2/201810/2/201810/2/2018 1:19:24 PMPPASS
Phone #: ###-#### Inspection requested via web by Ashley Rasmussen Ok final
ELE18-02810 Final10/1/201810/2/201810/2/2018 11:42:47 AMAPASS
Phone #: ###-#### Inspection requested via web by Chris Berthelot Ok final.
ELE18-03475 Final9/25/201810/2/201810/2/2018 11:12:51 AMANR
Electrical Final Any Questions Please Call Louis At ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller
ELE18-03716 Rough-In Permanent Service10/1/201810/2/201810/2/2018 11:00:29 AMAPASS
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk p/s u/g n ok
ELE18-03760 Final10/1/201810/2/201810/2/2018 11:00:12 AMAPASS
If you would please call Rick at ###-#### - 30 mins to Inspection ; he will meet you for access and any questions! Thx. Steve, BPL Phone #: ###-#### Inspection requested via web by Steven Meredith Ok final. No bonding required. GFI functions properly.
ELE18-03644 Final10/1/201810/2/201810/2/2018 10:59:42 AMAPASS
730am for inspection..Talked to homeowner yesterday at 2pm to re-schedule. Ok final.
ELE18-03697 Electrical Rough-In10/1/201810/2/201810/2/2018 10:02:24 AMAFAIL
Phone #: ###-#### Inspection requested via web by Josh Pennington
1. 110.26 Gas meter located in front of new panel location. Could present unsafe working clearance.
2. 250.104(B) Metal conduit feeding meter to new panel needs bonded on accessible side.
3. Verify size of SER feeding interior panel.
4. Verify GEC termination to ground rod or UFER. If cannot verify, 2 ground rods will be installed.
5. Any box mounted with unacceptable means, wil need to be replaced with new. 2 gang back of house is mounted with screws through side of box.
6. It appears IDP meter tab has been tampered with. It looks like metal clip has been pulled apart and re-inserted.
ELE18-03705 Electrical Rough-In10/1/201810/2/201810/1/2018 1:51:27 PMACANC
Phone #: ###-#### >> Inspection requested via web by Josh Pennington Inspection cancelled from web by: Josh Pennington