Inspections for the day of: Wednesday, October 20, 2004.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00368 INSP-Sprinkler Rough-in10/18/200410/20/200410/20/2004 12:00:00 AMAFAIL
eric; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Gatehouse area: Hangers and EQ bracing on webbing - move to top chord or provide written engineeering approval 10/20/2004 10:40:46 AM
BLD04-01338 FIRE-Final Inspection10/19/200410/20/200410/20/2004 12:00:00 AMAPASS
jack; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 10/20/2004 11:59:02 AM
FIR04-00619 INSP-Sprinkler Rough-in/Hydro10/20/200410/20/200410/20/2004 12:00:00 AMAFAIL
To verify FDC and vault installation. Re submitted plans are in job trailer.; Phone #: ###-#### Internet Inspection Request from: Trent Bice Need gravel in pit; ball valve will have to be removed after hydro 10/20/2004 11:31:07 AM
FIR04-00272 INSP-Sprinkler Rough-in/Hydro10/20/200410/20/200410/20/2004 12:00:00 AMPNR
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Not ready for inspection 10/20/2004 1:48:18 PM
FIR04-00175 INSP-Sprinkler Rough-in/Hydro10/20/200410/20/200410/20/2004 12:00:00 AMPFAIL
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Sidewalls need to be 4-6 inches below ceiling; straps on second floor; EQ riser; hydro okay FDC will need hydro 10/20/2004 4:05:50 PM
FIR04-00214 INSP-Sprinkler Rough-in/Hydro10/20/200410/20/200410/20/2004 12:00:00 AMPPART
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Hydro and r/i okay; need FDC hydro 10/20/2004 4:06:11 PM
BLD04-01962 FIRE-Final Inspection10/20/200410/20/200410/20/2004 12:00:00 AMPPASS
allen; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIR04-00245 INSP-Final Inspection10/20/200410/20/200410/20/2004 12:00:00 AMPPART
Hi Rick, We have the doors working and F/S all been gone thru. thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble Need to verify door closures to OR's with fire alarm; all other items corrected - need NFPA 72 record of completion 10/20/2004 4:03:19 PM
BLD04-01212 FIRE-Final Inspection10/20/200410/20/200410/20/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/20/2004 at 7:06:52 AM. Contact: ###-####.