ELE05-02247
| Final | 10/20/2005 | 10/20/2005 | 10/20/2005 3:56:16 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE05-02246
| Final | 10/20/2005 | 10/20/2005 | 10/20/2005 3:55:58 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE05-02248
| Final | 10/20/2005 | 10/20/2005 | 10/20/2005 3:55:38 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE05-00419
| Permanent Service | 10/20/2005 | 10/20/2005 | 10/20/2005 2:25:29 PM | P | FAIL |
|
|
kevin ###-#### 110.26 clearence for p/s, needs all grounding and bonding done, 230.6 service entrance conductors not allowed in building needs main outside and all gear in will be sub panels, is bldg #9 one or two buildings if one only one p/s allowed
|
ELE05-00119
| Permanent Service | 10/20/2005 | 10/20/2005 | 10/20/2005 2:17:10 PM | P | FAIL |
|
|
kevin ###-#### calc service out, needs all grounding and bonding done met contractor
|
ELE05-02213
| Rough-In Permanent Service | 10/20/2005 | 10/20/2005 | 10/20/2005 2:15:16 PM | P | NR |
|
|
kevin ###-#### met contractor
|
ELE05-02781
| Final | 10/19/2005 | 10/20/2005 | 10/20/2005 2:14:50 PM | P | NR |
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called missing outside light fixture and what is coiled up ser cable for?
|
ELE05-03825
| Electrical Rough-In | 10/19/2005 | 10/20/2005 | 10/20/2005 11:03:07 AM | A | FAIL |
|
|
###-#### - nichole cor. called left message 314.16 box fill 300.4 nail pltes and 11/4", 410.8 clearence closet light upstairs bed rm over garage, 250.148 splice all equip grds 12 1nd 14 together
|
ELE05-03512
| Final | 10/19/2005 | 10/20/2005 | 10/20/2005 10:39:03 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 10/19/2005 at 7:36:33 PM. Contact: ###-####. ok card signed
|
ELE05-03826
| Temporary Service | 10/19/2005 | 10/20/2005 | 10/20/2005 10:25:17 AM | A | NR |
|
|
warren ###-#### called needs to wire job shack
|
ELE05-02693
| Final | 10/19/2005 | 10/20/2005 | 10/20/2005 9:58:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohlok
|
ELE05-02721
| Final | 10/20/2005 | 10/20/2005 | 10/20/2005 9:57:41 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkmanok
|
ELE05-03824
| Rough-In Permanent Service | 10/19/2005 | 10/20/2005 | 10/20/2005 9:31:50 AM | A | PASS |
|
|
jim ###-#### r/i ok p/s u/g new ok
|
ELE05-03577
| Permanent Service | 10/19/2005 | 10/20/2005 | 10/20/2005 9:04:59 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty p/s u/g new ok
|
ELE05-03821
| Rough-In Permanent Service | 10/19/2005 | 10/20/2005 | 10/20/2005 8:10:26 AM | A | PASS |
|
|
zane ###-#### r/i ok p/s o/h new ok
|