Inspections for the day of: Thursday, October 20, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02247 Final10/20/200510/20/200510/20/2005 3:56:16 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE05-02246 Final10/20/200510/20/200510/20/2005 3:55:58 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE05-02248 Final10/20/200510/20/200510/20/2005 3:55:38 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE05-00419 Permanent Service10/20/200510/20/200510/20/2005 2:25:29 PMPFAIL
kevin ###-#### 110.26 clearence for p/s, needs all grounding and bonding done, 230.6 service entrance conductors not allowed in building needs main outside and all gear in will be sub panels, is bldg #9 one or two buildings if one only one p/s allowed
ELE05-00119 Permanent Service10/20/200510/20/200510/20/2005 2:17:10 PMPFAIL
kevin ###-#### calc service out, needs all grounding and bonding done met contractor
ELE05-02213 Rough-In Permanent Service10/20/200510/20/200510/20/2005 2:15:16 PMPNR
kevin ###-#### met contractor
ELE05-02781 Final10/19/200510/20/200510/20/2005 2:14:50 PMPNR
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called missing outside light fixture and what is coiled up ser cable for?
ELE05-03825 Electrical Rough-In10/19/200510/20/200510/20/2005 11:03:07 AMAFAIL
###-#### - nichole cor. called left message 314.16 box fill 300.4 nail pltes and 11/4", 410.8 clearence closet light upstairs bed rm over garage, 250.148 splice all equip grds 12 1nd 14 together
ELE05-03512 Final10/19/200510/20/200510/20/2005 10:39:03 AMAPASS
Scheduled by a contractor via Hello! on 10/19/2005 at 7:36:33 PM. Contact: ###-####. ok card signed
ELE05-03826 Temporary Service10/19/200510/20/200510/20/2005 10:25:17 AMANR
warren ###-#### called needs to wire job shack
ELE05-02693 Final10/19/200510/20/200510/20/2005 9:58:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dan Rohlok
ELE05-02721 Final10/20/200510/20/200510/20/2005 9:57:41 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkmanok
ELE05-03824 Rough-In Permanent Service10/19/200510/20/200510/20/2005 9:31:50 AMAPASS
jim ###-#### r/i ok p/s u/g new ok
ELE05-03577 Permanent Service10/19/200510/20/200510/20/2005 9:04:59 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty p/s u/g new ok
ELE05-03821 Rough-In Permanent Service10/19/200510/20/200510/20/2005 8:10:26 AMAPASS
zane ###-#### r/i ok p/s o/h new ok