FIR05-00426
| INSP-Alarm Testing | 10/20/2005 | 10/20/2005 | 10/20/2005 4:51:01 PM | A | CANC |
|
|
The shell permit must be finaled prior to final acceptance of the TI permit, no time for this inspection today.
|
FIR05-00075
| INSP-Alarm Testing | 10/20/2005 | 10/20/2005 | 10/20/2005 4:47:39 PM | P | FAIL |
|
|
PIV tamper failed to function properly, the north elevator failed to recall upon smoke detection, the west elevator is not completed to allow testing, elevator control voltage needs to be monitored as a supervisory not a trouble signal, provide a sign at the door to the FACP, testing not completed today due to time constraints.
|
FIR05-00089
| INSP-Final Inspection | 10/20/2005 | 10/20/2005 | 10/20/2005 4:39:46 PM | P | FAIL |
|
|
PIV tamper is not adjusted correctly, the flow switch operates intermittently causing the outside bell to cycle on and off, no overhead looked at today due to time constraints.
|
BLD05-01279
| FIRE-Final Inspection | 10/19/2005 | 10/20/2005 | 10/20/2005 3:39:59 PM | P | FAIL |
|
|
Provide approved door hardware at driver and dispatcher room doors--must be opened in a single motion without the use of a key or special knowledge or effort, provide signage at express room door if keyed locking hardware is to remain or remove deadbolt, see plan review note #1 for door hardware requirements.
|
BLD05-01979
| FIRE-Final Inspection | 10/20/2005 | 10/20/2005 | 10/20/2005 2:46:26 PM | P | FAIL |
|
|
Door at NE corner needs approved hardware, provide building address numbers min. 4" high facing the street to which building is addressed, provide knox box.
|
BLD05-01979
| FIRE-Alarm Testing | 10/20/2005 | 10/20/2005 | 10/20/2005 2:44:30 PM | P | FAIL |
|
|
Door at NE corner needs approved hardware, provide building address numbers min. 4" high, provide knox box.
|
BLD05-02844
| FIRE-Final Inspection | 10/20/2005 | 10/20/2005 | 10/20/2005 2:43:09 PM | P | FAIL |
|
|
The door at northeast side needs approved hardware installed, the shell permit must be finaled prior to the TI, shell needs building address and a knox box.
|
BLD05-02844
| FIRE-Alarm Testing | 10/20/2005 | 10/20/2005 | 10/20/2005 2:40:56 PM | P | FAIL |
|
|
The exit door at northeast side needs approved hardware installed, the shell permit must be finaled prior to TI which needs building address numbers and a knox box installed.
|
BLD05-02031
| FIRE-Final Inspection | 10/20/2005 | 10/20/2005 | 10/20/2005 2:38:20 PM | P | FAIL |
|
|
The HVAC duct smoke detector failed to activate.
|
BLD05-02031
| FIRE-Alarm Testing | 10/20/2005 | 10/20/2005 | 10/20/2005 2:37:35 PM | P | FAIL |
|
|
The HVAC duct smoke detector failed to activate.
|
BLD05-01980
| FIRE-Final Inspection | 10/20/2005 | 10/20/2005 | 10/20/2005 2:36:38 PM | P | FAIL |
|
|
HVAC duct smoke detector failed to activate.
|
BLD05-01980
| FIRE-Alarm Testing | 10/20/2005 | 10/20/2005 | 10/20/2005 2:35:38 PM | P | FAIL |
|
|
HVAC duct smoke detector failed to activate.
|
FIR05-00462
| INSP-Sprinkler Rough-in/Hydro | 10/19/2005 | 10/20/2005 | 10/20/2005 1:38:48 PM | P | PASS |
|
|
This inspection was for a final on the alarm permit which passed.
|
FIR05-00372
| INSP-Sprinkler Rough-in/Hydro | 10/19/2005 | 10/20/2005 | 10/20/2005 11:16:09 AM | A | PART |
|
|
Witnessed testing and start up of the fire pump, tested at 150%, 100%, rated flow and shutoff, tested jockey pump, need to run drain from pump casing, need to install sensing lines per NFPA 20.
|
FIR05-00372
| INSP-Sprinkler Rough-in | 10/18/2005 | 10/20/2005 | 10/20/2005 11:08:48 AM | A | NR |
|
|
Per Matt the shell rough-in is not ready for inspection at this time.
|
FIR05-00459
| INSP-Alarm Testing | 10/18/2005 | 10/20/2005 | 10/20/2005 8:57:12 AM | A | NR |
|
|
Work is not complete per discussion with contractor, inspection to be rescheduled.
|
BLD04-01076
| FIRE-Final Inspection | 10/19/2005 | 10/20/2005 | 10/20/2005 8:37:35 AM | A | FAIL |
|
|
Provide one 2A10BC fire ext. with current inspection tag, provide approved door hardware at exit door as discussed.
|