Inspections for the day of: Friday, October 20, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00090 INSP-Final Inspection10/20/200610/20/200610/23/2006 12:51:28 PMPCANC
Inspection to be rescheduled per agreement.
FIR05-00772 INSP-Sprinkler Rough-in/Hydro10/19/200610/20/200610/20/2006 3:35:54 PMPPART
UG fire supply line hydro test is satisfactory.
FIR05-00425 INSP-Sprinkler Rough-in10/19/200610/20/200610/20/2006 3:29:15 PMAPART
Piping in the pool room 5th floor matches plans provided, calcs for this remote area to be verified by plan reviewer at resubmittal.
FIR06-00649 INSP-Final Inspection10/19/200610/20/200610/20/2006 2:50:15 PMAPART
Fire alarm tested okay, the sample and vent tubes on one duct detector are reversed.
BLD06-01860 FIRE-Final Inspection10/19/200610/20/200610/20/2006 2:48:39 PMPFAIL
The project related fire sprinkler permit must be finaled prior to life safety final, also missing PFE, project is not in a condition for final life safety inspection at this time.
BLD06-01553 FIRE-Final Inspection10/19/200610/20/200610/20/2006 2:46:07 PMPPASS
Required corrections have been made, inspection passed.
FIR06-00606 INSP-Final Inspection10/19/200610/20/200610/20/2006 2:44:27 PMAPASS
Fire alarm work is satisfactory, permit finaled.
FIR06-00753 INSP-Sprinkler Rough-in/Hydro10/19/200610/20/200610/20/2006 12:01:44 PMANR
Hydrostatic test for the UG to be rescheduled.
FIR06-00753 INSP-Supply line flush10/19/200610/20/200610/20/2006 11:37:37 AMAPART
UG fire supply line flush performed satisfactory.
FIR06-00596 INSP-Alarm Testing10/18/200610/20/200610/20/2006 10:42:45 AMANR
rob - note: fire alarm only - 6th floor ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Sufficient visual notification coverage at ADA room 10x cannot yet be determined due to missing room finishes and hardware, door holders are not ready for inspection, elevator is not ready for inspection. Coverage at the SW ADA room and adjacent corridor is acceptable.
FIR06-00558 INSP-Sprinkler Rough-in10/19/200610/20/200610/20/2006 10:28:03 AMAPART
OH rough in at the ground floor section A surgery waiting is okay to cover except one area as circled on approved plans which is overspaced.
FIR06-00560 INSP-Sprinkler Rough-in10/19/200610/20/200610/20/2006 10:26:10 AMAPART
OH rough-in is good for cover at the drop ceiling areas.
FIR06-00595 INSP-Alarm Testing10/17/200610/20/200610/20/2006 9:32:42 AMAFAIL
Testing for the 2nd floor NE quad only, need to relocate one notifcation device as marked on plans for proper coverage, missing one h/s at the west side division between quadrants, added sd at the electrical room to be shown on plans.