Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00264 INSP-Final Inspection10/20/200910/20/200910/21/2009 9:46:49 AMPNH
Need the fire sprinkler contractor representative on site to complete functional trip testing of the new dry system valve and appurtenances.
BLD09-01139 FIRE-Final Inspection10/20/200910/20/200910/20/2009 4:46:00 PMPFAIL
Noted one missing fire alarm notification device at the short hall adjacent to the new conference room- appliance is detatched and wiring at the junction box is exposed. Remainder of fire life safety okayed.
FIR09-00523 INSP-Alarm Testing10/20/200910/20/200910/20/2009 4:41:24 PMPNR
Contact phone#: ###-####
BLD09-01825 FIRE-Final Inspection10/20/200910/20/200910/20/2009 4:41:08 PMPFAIL
Correction items include repair one exit sign, post max. occupant load sign, provide current annual certification tags for the fire extinguishers, replace ceiling tile at the bar area, provide verification of current inspections for the building fire sprinkler and alarm systems.
FIR09-00577 INSP-Sprinkler Rough-in10/20/200910/20/200910/20/2009 4:36:49 PMPPART
Scope of fire sprinkler work per revised permit documents passed inspection and okayed for cover, final pending ceiling tile and escutcheons.
FIR09-00304 INSP-Final Inspection10/19/200910/20/200910/20/2009 4:34:42 PMAPART
New panel and sprinkler riser supervision tested okay however account information at offsite monitoring including zone descriptors and building address was not set up, temporal pattern at notification in the apartment unit 516 (101, 201) corrected while on site.
BLD09-00650 FIRE-Final Inspection10/19/200910/20/200910/20/2009 4:26:47 PMANR
Need project related fire alarm permit final prior to building fire life safety approvals.
FIR09-00384 INSP-Sprinkler Rough-in/Hydro10/20/200910/20/200910/20/2009 4:24:29 PMAPART
Jake Phone#: ###-####
BLD08-02268 FIRE-Conference10/20/200910/20/200910/20/2009 4:24:13 PMADONE
Regarding project related fire sprinkler permit work.