FIR09-00264
| INSP-Final Inspection | 10/20/2009 | 10/20/2009 | 10/21/2009 9:46:49 AM | P | NH |
|
|
Need the fire sprinkler contractor representative on site to complete functional trip testing of the new dry system valve and appurtenances.
|
BLD09-01139
| FIRE-Final Inspection | 10/20/2009 | 10/20/2009 | 10/20/2009 4:46:00 PM | P | FAIL |
|
|
Noted one missing fire alarm notification device at the short hall adjacent to the new conference room- appliance is detatched and wiring at the junction box is exposed. Remainder of fire life safety okayed.
|
FIR09-00523
| INSP-Alarm Testing | 10/20/2009 | 10/20/2009 | 10/20/2009 4:41:24 PM | P | NR |
|
|
Contact phone#: ###-####
|
BLD09-01825
| FIRE-Final Inspection | 10/20/2009 | 10/20/2009 | 10/20/2009 4:41:08 PM | P | FAIL |
|
|
Correction items include repair one exit sign, post max. occupant load sign, provide current annual certification tags for the fire extinguishers, replace ceiling tile at the bar area, provide verification of current inspections for the building fire sprinkler and alarm systems.
|
FIR09-00577
| INSP-Sprinkler Rough-in | 10/20/2009 | 10/20/2009 | 10/20/2009 4:36:49 PM | P | PART |
|
|
Scope of fire sprinkler work per revised permit documents passed inspection and okayed for cover, final pending ceiling tile and escutcheons.
|
FIR09-00304
| INSP-Final Inspection | 10/19/2009 | 10/20/2009 | 10/20/2009 4:34:42 PM | A | PART |
|
|
New panel and sprinkler riser supervision tested okay however account information at offsite monitoring including zone descriptors and building address was not set up, temporal pattern at notification in the apartment unit 516 (101, 201) corrected while on site.
|
BLD09-00650
| FIRE-Final Inspection | 10/19/2009 | 10/20/2009 | 10/20/2009 4:26:47 PM | A | NR |
|
|
Need project related fire alarm permit final prior to building fire life safety approvals.
|
FIR09-00384
| INSP-Sprinkler Rough-in/Hydro | 10/20/2009 | 10/20/2009 | 10/20/2009 4:24:29 PM | A | PART |
|
|
Jake Phone#: ###-####
|
BLD08-02268
| FIRE-Conference | 10/20/2009 | 10/20/2009 | 10/20/2009 4:24:13 PM | A | DONE |
|
|
Regarding project related fire sprinkler permit work.
|