ESC11-00581
| Aging Inspection | 10/20/2011 | 10/20/2011 | 10/21/2011 9:33:57 AM | | DONE |
|
|
looked ok
|
ELE10-02055
| ELE-Aging Inspection | 10/20/2011 | 10/20/2011 | 10/20/2011 3:02:56 PM | | DONE |
|
|
still under construction
|
ELE10-02067
| ELE-Aging Inspection | 10/20/2011 | 10/20/2011 | 10/20/2011 3:01:57 PM | | DONE |
|
|
still under constructiojn
|
ELE10-02455
| ELE-Aging Inspection | 10/20/2011 | 10/20/2011 | 10/20/2011 3:01:00 PM | | DONE |
|
|
still under construction
|
ELE11-02397
| Final | 10/20/2011 | 10/20/2011 | 10/20/2011 2:48:47 PM | P | PASS |
|
|
>> Inspection requested via web by Terry Scott ok final
|
ELE11-02023
| Final | 10/20/2011 | 10/20/2011 | 10/20/2011 2:37:52 PM | P | PASS |
|
|
Final. CJ is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut ok final, signed card
|
ELE11-02378
| Permanent Service | 10/20/2011 | 10/20/2011 | 10/20/2011 1:58:55 PM | P | PASS |
|
|
Need partial inspection on new service so Idaho power can change over,any questions call Jake @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose p/s o/h rec ok
|
ELE11-01931
| Final | 10/18/2011 | 10/20/2011 | 10/20/2011 12:45:33 PM | P | PASS |
|
|
Greg is the contact his no.###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates ok final, signed card
|
ELE11-01249
| Electrical Rough-In | 10/20/2011 | 10/20/2011 | 10/20/2011 12:03:08 PM | P | PASS |
|
|
RYKER Phone #: ###-#### ok cover ceiling larger room, center part building
|
ELE11-01416
| Final | 10/19/2011 | 10/20/2011 | 10/20/2011 10:34:10 AM | A | CANC |
|
|
Contact Kelly Tarter 30mins prior to inspection Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson called, contractor asked to cancel, had not done panel schedule, will recall when done
|
ELE11-02394
| Permanent Service | 10/19/2011 | 10/20/2011 | 10/20/2011 10:22:20 AM | A | FAIL |
|
|
call before//Charles Phone #: ###-#### owner shall provide continuous ground to panel, provide 8' roof clearance for service conductors, strap conduit within 3' of panel
|
ELE11-02004
| Electrical Rough-In | 10/19/2011 | 10/20/2011 | 10/20/2011 10:07:59 AM | A | PASS |
|
|
Underground Inspection-Taxiways A/D. Contact is Sean Sivesind ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok cover u/g
|
ELE11-00557
| Electrical Rough-In | 10/19/2011 | 10/20/2011 | 10/20/2011 9:19:49 AM | A | PASS |
|
|
Contact is Deeon Martineau ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok cover walls anop
|
ELE11-02396
| Rough-In Permanent Service | 10/20/2011 | 10/20/2011 | 10/20/2011 8:35:18 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, left correction notice, NEC 110.26(F)(1)(a) there shall be no foreign piping systems in dedicated electrical space, 334.30 shall staple nm cable wirhin 12" of panel, 210.52(A)(1) no point along floor line shall be over 6' from outlet,334.23 shall protect cable within 6' of attic access
|