Inspections for the day of: Thursday, October 20, 2011.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC11-00581 Aging Inspection10/20/201110/20/201110/21/2011 9:33:57 AM DONE
looked ok
ELE10-02055 ELE-Aging Inspection10/20/201110/20/201110/20/2011 3:02:56 PM DONE
still under construction
ELE10-02067 ELE-Aging Inspection10/20/201110/20/201110/20/2011 3:01:57 PM DONE
still under constructiojn
ELE10-02455 ELE-Aging Inspection10/20/201110/20/201110/20/2011 3:01:00 PM DONE
still under construction
ELE11-02397 Final10/20/201110/20/201110/20/2011 2:48:47 PMPPASS
>> Inspection requested via web by Terry Scott ok final
ELE11-02023 Final10/20/201110/20/201110/20/2011 2:37:52 PMPPASS
Final. CJ is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut ok final, signed card
ELE11-02378 Permanent Service10/20/201110/20/201110/20/2011 1:58:55 PMPPASS
Need partial inspection on new service so Idaho power can change over,any questions call Jake @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose p/s o/h rec ok
ELE11-01931 Final10/18/201110/20/201110/20/2011 12:45:33 PMPPASS
Greg is the contact his no.###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates ok final, signed card
ELE11-01249 Electrical Rough-In10/20/201110/20/201110/20/2011 12:03:08 PMPPASS
RYKER Phone #: ###-#### ok cover ceiling larger room, center part building
ELE11-01416 Final10/19/201110/20/201110/20/2011 10:34:10 AMACANC
Contact Kelly Tarter 30mins prior to inspection Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson called, contractor asked to cancel, had not done panel schedule, will recall when done
ELE11-02394 Permanent Service10/19/201110/20/201110/20/2011 10:22:20 AMAFAIL
call before//Charles Phone #: ###-#### owner shall provide continuous ground to panel, provide 8' roof clearance for service conductors, strap conduit within 3' of panel
ELE11-02004 Electrical Rough-In10/19/201110/20/201110/20/2011 10:07:59 AMAPASS
Underground Inspection-Taxiways A/D. Contact is Sean Sivesind ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok cover u/g
ELE11-00557 Electrical Rough-In10/19/201110/20/201110/20/2011 9:19:49 AMAPASS
Contact is Deeon Martineau ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok cover walls anop
ELE11-02396 Rough-In Permanent Service10/20/201110/20/201110/20/2011 8:35:18 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, left correction notice, NEC 110.26(F)(1)(a) there shall be no foreign piping systems in dedicated electrical space, 334.30 shall staple nm cable wirhin 12" of panel, 210.52(A)(1) no point along floor line shall be over 6' from outlet,334.23 shall protect cable within 6' of attic access