Inspections for the day of: Tuesday, October 20, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00835 ELE-Aging Inspection10/20/201510/20/201510/27/2015 3:57:04 PM DONE
Still under construction
ELE13-00542 ELE-Aging Inspection10/20/201510/20/201510/27/2015 3:51:40 PM DONE
Still under construction
ELE15-02857 Final10/20/201510/20/201510/20/2015 1:44:56 PMPFAIL
Phone #: ###-#### Inspection requested via web by Will Sevy
314.20- Boxes not flush with combustable or recessed more than a 1/4" shall have box extenders installed.
352.30- PVC service riser shall be secured with in 3' of meter enclosure.
ELE15-01111 Electrical Rough-In10/19/201510/20/201510/20/2015 12:57:14 PMPPASS
We need a ceiling inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
Service receiving, service waiting, parts sales, accessory room grid rough in ok cover.
ELE15-03367 Electrical Rough-In10/19/201510/20/201510/20/2015 11:17:47 AMACANC
Please call Shane ###-#### when you are on your way, he should be there. Thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan
Called contact and contractor to inform them unable to do inspection due to BLD permit is still under review and to recall when permit has been issued.
ELE15-01018 Final10/19/201510/20/201510/20/2015 10:57:28 AMAPASS
Kristian Phone #: ###-#### Final ok
ELE15-02122 Electrical Rough-In10/19/201510/20/201510/20/2015 10:28:01 AMAFAIL
Dennis Phone #: ###-#### 210.52- Receptacle outlet shall be located with in 6' of a door opening, then with in 12' of previous receptacle.
334.30- NM cable shall be secured 1 1/4" from framing surface and shall not be stapled on edge.
ELE15-02598 Electrical Rough-In10/19/201510/20/201510/20/2015 9:28:54 AMAPASS
Ceiling inspect for storage hallway behind customer service area. Access code is 2508. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Hall grid rough in ok cover
ELE15-03362 Rough-In Permanent Service10/19/201510/20/201510/20/2015 8:52:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
310.15(B)(7)(1)- Service entrance conductors. 200a x .83=166amps, 75 degree only, 2/0 minimum shall be used.
ELE15-03362 Electrical Rough-In10/20/201510/20/201510/20/2015 8:49:48 AMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn House only rough in ok cover.