ELE15-00089
| Permanent Service | 10/20/2015 | 10/20/2015 | 10/20/2015 1:35:11 PM | P | PASS |
|
|
Call prior to going Phone #: 2083520355 >> Inspection requested via mobile web by Dan monzo p/s o/h rec ok will look for second ground rod at next inspection
|
ELE15-03377
| Electrical Rough-In | 10/20/2015 | 10/20/2015 | 10/20/2015 12:48:21 PM | P | PASS |
|
|
We need a Ufer inspection for today. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker r/i ok ufer
|
ELE13-01341
| ELE-Aging Inspection | 10/20/2015 | 10/20/2015 | 10/20/2015 11:41:19 AM | | DONE |
|
|
homeowner hired Edwards electric on permit ele14-00506 at was finaled
|
ELE13-01341
| DOC - Permit Finaled | 10/20/2015 | 10/20/2015 | 10/20/2015 11:40:28 AM | P | PASS |
|
|
homeowner hired Edwards electric on permit ele14-00506 at was inspected and finaled
|
ESC15-00271
| General Inspection | 10/20/2015 | 10/20/2015 | 10/20/2015 11:19:19 AM | A | PASS |
|
|
no issues jobsite is clean and no track out (ok for all esc permits at this site)
|
ELE15-02073
| Final | 10/19/2015 | 10/20/2015 | 10/20/2015 11:08:16 AM | A | PASS |
|
|
The access code is either 1234 or 2468, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren final ok
|
ELE15-01936
| Final | 10/19/2015 | 10/20/2015 | 10/20/2015 11:07:25 AM | A | PASS |
|
|
The access code is either 1234 or 2468, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren corrections made final ok
|
ELE15-02124
| Final | 10/19/2015 | 10/20/2015 | 10/20/2015 10:51:55 AM | A | PASS |
|
|
The access code is either 1234 or 2468, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren final ok
|
ELE15-02258
| Final | 10/19/2015 | 10/20/2015 | 10/20/2015 10:27:09 AM | A | PASS |
|
|
The access code is either 1234 or 2468, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren final ok
|
ELE15-02960
| Electrical Rough-In | 10/19/2015 | 10/20/2015 | 10/20/2015 9:28:52 AM | A | PASS |
|
|
Ceiling Inspection for One Capital Center. Contact Jon Novak ###-#### Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek r/i ok 6th floor south half t bar ceilings ok
|
ELE15-03372
| Conference | 10/19/2015 | 10/20/2015 | 10/20/2015 8:41:12 AM | A | DONE |
|
|
call to set up time to meet Phone #: ###-#### Inspection requested via web by steve sellers discuss sub panel installation on separate bldg. using existing 2" u.ground raceway. Make attempt to install equipment grounding conductor in raceway. If this cannot be accomplished, drive additional ground rod at house. Of course separate nutral and ground at new loadcenter.
|