ELE16-03016
| Final | 10/20/2016 | 10/20/2016 | 10/20/2016 4:21:37 PM | P | FAIL |
|
|
Lockbox on back side of building. Code is 0475. Phone #: ###-#### Inspection requested via web by Paula Gratiot 300.15- All boxes shall have covers. LT box at bot of stair. 408.7- unused openings shall be closed. brkr blank. Called left message
|
ELE16-03182
| Permanent Service | 10/20/2016 | 10/20/2016 | 10/20/2016 1:56:52 PM | P | PASS |
|
|
New panel installation in addition to existing service Phone #: ###-#### Inspection requested via web by Jerry Moore Metal underground water pipe for fire riser shall be included in grounding electrode system as per 250.50. Ground rods present. p/s o/h n ok
|
ELE16-03390
| Temporary Service | 10/20/2016 | 10/20/2016 | 10/20/2016 1:03:33 PM | P | PASS |
|
|
Corrections fixed. Contact is Toby Groves. ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves t/s o/h n ok
|
ELE13-02960
| Final | 10/19/2016 | 10/20/2016 | 10/20/2016 12:16:32 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Noeker Listing confirmed. Final ok
|
ELE15-01348
| Final | 10/19/2016 | 10/20/2016 | 10/20/2016 12:15:32 PM | A | NR |
|
|
Rock, I need to sign off on the permit rather than the matrix paper that Hoffman provided last week. Same levels just the official document Phone #: ###-#### Inspection requested via web by Tom Betty Official document includes all of HQ and annex. Unable to sign would release all area described on BLD permit. General contractor will develope a sheet for progress to document which areas are ready to occupy.
|
ELE16-01838
| Final | 10/19/2016 | 10/20/2016 | 10/20/2016 12:14:58 PM | A | NR |
|
|
Rock, I need to sign off on the permit rather than the Matrix paperwork provided by Hoffman last week. Phone #: ###-#### Inspection requested via web by Tom Betty Official document includes all of HQ and annex. Unable to sign would release all area described on BLD permit. General contractor will develope a sheet for progress to document which areas are ready to occupy.
|
ELE16-02250
| Final | 10/19/2016 | 10/20/2016 | 10/20/2016 11:16:40 AM | A | NR |
|
|
this was a job we never pulled wire on. just conference with an inspector. i will be out of cell service just for the day tomorrow. thanks, greg Phone #: ###-#### Inspection requested via web by Greg Idsinga 2nd permit ELE16-03190 exists by other contractor on address not sure who is doing work shall recall when clearified.
|
ELE14-00140
| Final | 10/19/2016 | 10/20/2016 | 10/20/2016 9:18:51 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Noeker Dupicate request Final ok
|
ELE14-00140
| Final | 10/19/2016 | 10/20/2016 | 10/20/2016 9:18:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Noeker Final ok
|
ELE14-00140
| Electrical Rough-In | 10/20/2016 | 10/20/2016 | 10/20/2016 8:59:16 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Noeker Listing and disconnecting means confirmed rough in ok
|
ELE14-03193
| Final | 10/19/2016 | 10/20/2016 | 10/20/2016 8:58:12 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Noeker Final ok
|
ELE14-03193
| Electrical Rough-In | 10/20/2016 | 10/20/2016 | 10/20/2016 8:51:26 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Noeker Listing confirmed rough in ok
|
ELE15-00644
| Final | 10/19/2016 | 10/20/2016 | 10/20/2016 8:41:21 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Noeker Final ok
|
ELE15-00644
| Electrical Rough-In | 10/20/2016 | 10/20/2016 | 10/20/2016 8:41:03 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Noeker Listing confirmed rough in ok
|