Inspections for the day of: Thursday, October 20, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03016 Final10/20/201610/20/201610/20/2016 4:21:37 PMPFAIL
Lockbox on back side of building. Code is 0475. Phone #: ###-#### Inspection requested via web by Paula Gratiot
300.15- All boxes shall have covers. LT box at bot of stair.
408.7- unused openings shall be closed. brkr blank.
Called left message
ELE16-03182 Permanent Service10/20/201610/20/201610/20/2016 1:56:52 PMPPASS
New panel installation in addition to existing service Phone #: ###-#### Inspection requested via web by Jerry Moore
Metal underground water pipe for fire riser shall be included in grounding electrode system as per 250.50. Ground rods present. p/s o/h n ok
ELE16-03390 Temporary Service10/20/201610/20/201610/20/2016 1:03:33 PMPPASS
Corrections fixed. Contact is Toby Groves. ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
t/s o/h n ok
ELE13-02960 Final10/19/201610/20/201610/20/2016 12:16:32 PMAPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Listing confirmed. Final ok
ELE15-01348 Final10/19/201610/20/201610/20/2016 12:15:32 PMANR
Rock, I need to sign off on the permit rather than the matrix paper that Hoffman provided last week. Same levels just the official document Phone #: ###-#### Inspection requested via web by Tom Betty
Official document includes all of HQ and annex. Unable to sign would release all area described on BLD permit. General contractor will develope a sheet for progress to document which areas are ready to occupy.
ELE16-01838 Final10/19/201610/20/201610/20/2016 12:14:58 PMANR
Rock, I need to sign off on the permit rather than the Matrix paperwork provided by Hoffman last week. Phone #: ###-#### Inspection requested via web by Tom Betty
Official document includes all of HQ and annex. Unable to sign would release all area described on BLD permit. General contractor will develope a sheet for progress to document which areas are ready to occupy.
ELE16-02250 Final10/19/201610/20/201610/20/2016 11:16:40 AMANR
this was a job we never pulled wire on. just conference with an inspector. i will be out of cell service just for the day tomorrow.
thanks, greg Phone #: ###-#### Inspection requested via web by Greg Idsinga
2nd permit ELE16-03190 exists by other contractor on address not sure who is doing work shall recall when clearified.
ELE14-00140 Final10/19/201610/20/201610/20/2016 9:18:51 AMPPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Dupicate request Final ok
ELE14-00140 Final10/19/201610/20/201610/20/2016 9:18:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Final ok
ELE14-00140 Electrical Rough-In10/20/201610/20/201610/20/2016 8:59:16 AMPPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Listing and disconnecting means confirmed rough in ok
ELE14-03193 Final10/19/201610/20/201610/20/2016 8:58:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Final ok
ELE14-03193 Electrical Rough-In10/20/201610/20/201610/20/2016 8:51:26 AMPPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Listing confirmed rough in ok
ELE15-00644 Final10/19/201610/20/201610/20/2016 8:41:21 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Final ok
ELE15-00644 Electrical Rough-In10/20/201610/20/201610/20/2016 8:41:03 AMPPASS
Phone #: ###-#### Inspection requested via web by Tom Noeker
Listing confirmed rough in ok