Inspections for the day of: Thursday, October 20, 2016.
Number of inspections: 26
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBen Livingston
TitleMEC-COM/RES INSPECTOR
Phone #576-1208
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC15-04672 Mec-Aging Inspection10/20/201610/20/201610/20/2016 4:42:43 PM CANC
MEC15-04672 DOC - Permit Expired10/20/201610/20/201610/20/2016 4:42:32 PMPPASS
MEC15-04623 Mec-Aging Inspection10/20/201610/20/201610/20/2016 3:58:12 PM CANC
MEC15-04623 DOC - Permit Expired10/20/201610/20/201610/20/2016 3:58:04 PMPPASS
MEC15-04673 Mec-Aging Inspection10/20/201610/20/201610/20/2016 3:48:06 PM CANC
MEC15-04673 DOC - Permit Expired10/20/201610/20/201610/20/2016 3:47:55 PMPPASS
MEC16-03506 Final10/20/201610/20/201610/20/2016 3:28:43 PMPPASS
Please call Daryl with any questions. Phone #: ###-#### Inspection requested via web by Diane Day
MEC16-04599 Final10/17/201610/20/201610/20/2016 3:10:12 PMPPASS
Please call Dwight @ ###-#### to make sure he''s ready for you. Thank you! Phone #: ###-#### Inspection requested via web by Rick Borg
MEC16-04352 Rough-in10/18/201610/20/201610/20/2016 2:44:13 PMPFAIL
Please call Daryl with any questions. Phone #: ###-#### Inspection requested via web by Diane Day
fresh air needs more sealer
MEC16-04352 Pressure Test10/18/201610/20/201610/20/2016 2:43:40 PMPPART
Please call Daryl with any questions. Phone #: ###-#### Inspection requested via web by Diane Day
60,20lb gas ok

gas pipe needs 10mill tape where it exits the building
5lb flue under 5lb
MEC16-04665 Final10/20/201610/20/201610/20/2016 1:54:58 PMPFAIL
Inspection requested via web by Margie Rowe
gas piping needs sediment trap before furnace, secondary condensate needs to go to conspiquous location or wet switch
MEC16-04143 Rough-in10/20/201610/20/201610/20/2016 1:19:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
20lb gas, rough in
MEC16-02812 Final10/19/201610/20/201610/20/2016 11:57:06 AMAPASS
Access #5296 Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
MEC16-04662 Rough-in10/20/201610/20/201610/20/2016 11:00:01 AMAPASS
Workers will usually get there about 9:00 -9:30, no equipment just ducting from existing system plus two vents and one dryer. Phone #: ###-#### Inspection requested via web by Bruce Lacy
MEC16-04662 Final10/20/201610/20/201610/20/2016 10:59:47 AMPPASS
Workers will usually get there about 9:00 -9:30, no equipment just ducting from existing system plus two vents and one dryer. Phone #: ###-#### Inspection requested via web by Bruce Lacy
MEC16-03249 Rough-in10/19/201610/20/201610/20/2016 10:08:16 AMAPASS
Will Phone #: ###-####
3rd floor ok for cover
MEC16-04217 Rough-in10/19/201610/20/201610/20/2016 10:08:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Dan Otero
MEC16-04611 Rough-in10/17/201610/20/201610/20/2016 9:32:07 AMAPASS
Inspection requested via web by Jason Robinson
MEC16-04143 Pressure Test10/19/201610/20/201610/20/2016 9:14:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
20lb gas , needs 10mill tape
MEC16-04143 Rough-in10/19/201610/20/201610/20/2016 9:10:13 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
8" supply feeding 2nd floor has a rip in the flex
MEC16-04582 Final10/19/201610/20/201610/20/2016 8:59:50 AMAPASS
Ben, this is the job that we spoke about with the confusion of the address. you tagged the fireplace for rough inspection. Give me a call on my cell Eddie ###-#### Phone #: ###-#### Inspection requested via web by John Horsfall
MEC16-04582 Rough-in10/20/201610/20/201610/20/2016 8:59:38 AMPPASS
Ben, this is the job that we spoke about with the confusion of the address. you tagged the fireplace for rough inspection. Give me a call on my cell Eddie ###-#### Phone #: ###-#### Inspection requested via web by John Horsfall
MEC16-04660 Rough-in10/19/201610/20/201610/20/2016 8:53:12 AMAPASS
Ben looked at these already but I needed to pull permit so I do not know if he has to go back out there, Phone #: ###-#### Inspection requested via web by Lori Dille
MEC16-04661 Rough-in10/19/201610/20/201610/20/2016 8:52:56 AMAPASS
Ben looked at these already but I needed to pull permit so I do not know if he has to go back out there, Phone #: ###-#### Inspection requested via web by Lori Dille
MEC16-01306 Mec-Aging Inspection10/20/201610/20/201610/20/2016 8:34:42 AM CANC
MEC16-01306 DOC - Permit Expired10/20/201610/20/201610/20/2016 8:34:34 AMPPASS