Inspections for the day of: Thursday, October 20, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00198 INSP-Alarm Testing10/20/201610/20/201610/20/2016 7:45:06 PMPDONE
Alarm testing complete for tamper switches and flow switches on wet pipe fire sprinkler systems located on levels 1 through 9 (signal verification still needs to be performed on level 1 simplot tower dry system). Items that still need inspected: audio/visual signals on parking level dry/standpipe systems as well as dry/standpipe systems being supplied from the JUMP fire pump, audio/visual devices on level 1 and parking level, elevator recall on all elevators, emergency fire door on level 1, in duct and smoke detectors on level 1 and parking level, stairwell pressurization on general alarm, fire alarm interface with kitchen hood monitoring and signal verification for commercial hood fire suppression activation, all fire alarm components associated with annex building and monitoring verification.
FIR15-00641 INSP-Final Inspection10/20/201610/20/201610/20/2016 7:22:52 PMPPART
Partial final for dry standpipes complete, all dry pipe valves associated with the dry standpipes have been tripped for proper valve operation. FIR permit will stay in issued status (Partial final for records) until BLD permit is ready to be finaled on life fire safety, at time of life fire safety completion FIR permit will be finaled as well.
FIR15-00602 INSP-Final Inspection10/20/201610/20/201610/20/2016 7:17:35 PMPPART
Final fire sprinkler inspection for level 1 simplot tower complete. This FIR permit is associated with levels 1 and 2 of the annex building, final inspection needs to be completed for the annex before this permit can be finaled. This FIR permit will also stay in issued status (Partial final for records) until BLD permit is ready to be finaled on life fire safety, at time of life fire safety completion FIR permit will be finaled as well.
FIR16-00275 INSP-Final Inspection10/20/201610/20/201610/20/2016 7:11:28 PMPPART
Final fire sprinkler inspection for level 6 and 7 complete. FIR permit will stay in issued status (Partial final for records) until BLD permit is ready to be finaled on life fire safety, at time of life fire safety completion FIR permit will be finaled as well.
FIR16-00146 INSP-Final Inspection10/20/201610/20/201610/20/2016 7:09:34 PMPPART
Final fire sprinkler inspection for levels 5 through 9 complete. FIR permit will stay in issued status (Partial final for records) until BLD permit is ready to be finaled on life fire safety, at time of life fire safety completion FIR permit will be finaled as well.
FIR16-00008 INSP-Final Inspection10/20/201610/20/201610/20/2016 7:09:00 PMPPART
Final fire sprinkler inspection for level 2 complete. FIR permit will stay in issued status (Partial final for records) until BLD permit is ready to be finaled on life fire safety, at time of life fire safety completion FIR permit will be finaled as well.
FIR16-00089 INSP-Final Inspection10/20/201610/20/201610/20/2016 7:06:38 PMPPART
Final fire sprinkler inspection for levels 3 & 4 complete. FIR permit will stay in issued status (Partial final for records) until BLD permit is ready to be finaled on life fire safety, at time of life fire safety completion FIR permit will be finaled as well.
BLD16-02523 FIRE-Final Inspection10/19/201610/20/201610/20/2016 1:36:28 PMPPASS
No fire sprinkler modifications (Fire sprinklers in area of work were replaced due to the existing heads being painted), final fire alarm inspection complete, fire extinguishers are in common area's with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00450 INSP-Sprinkler Rough-in10/19/201610/20/201610/20/2016 10:42:14 AMAFAIL
Tenting inspection performed for overhead fire sprinkler piping located in attic spaces done, piping cannot be covered, numerous area's throughout level 3 has insulation going over the top of plumbing vent lines, pocket between sheetrock and piping will not be formed due to the spacing. Level 3 west apartments has miising insulation over the top of the piping in the living rooms, piping cannot be covered at this time.
FIR16-00505 INSP-Final Inspection10/14/201610/20/201610/20/2016 10:13:03 AMAPASS
Final fire alarm inspection passed/complete.
BLD16-02395 FIRE-Final Inspection10/19/201610/20/201610/20/2016 9:55:34 AMPPASS
No fire sprinklers, no fire alarms, in-duct smoke detection is stand-alone, final commercial hood fire suppression system inspection is complete (FIR16-00622, permit is not attached to project related cases). Final life fire safety inspection passed/complete.
FIR16-00622 INSP-Final Inspection10/18/201610/20/201610/20/2016 9:53:24 AMAPASS
Final commercial hood fire suppression system inspection passed/complete.
FIR16-00531 INSP-Final Inspection10/19/201610/20/201610/19/2016 3:04:06 PMACANC
Inspection request completed on 19OCT2016, this request cancelled.