ELE13-00718
| ELE-Aging Inspection | 10/20/2017 | 10/20/2017 | 10/20/2017 2:07:46 PM | | FAIL |
|
|
Multiple attemps to contact contractor for scheduling final have gone unanswered. Still waiting on contractor
|
ELE17-01400
| Electrical Rough-In | 10/17/2017 | 10/20/2017 | 10/20/2017 2:05:29 PM | P | PASS |
|
|
Contact John for in slab rough in of LL2 west end concrete pour. Phone #: ###-#### Inspection requested via web by Tom Betty Area noted rough in ok cover
|
ELE17-01835
| Final | 10/19/2017 | 10/20/2017 | 10/20/2017 11:22:49 AM | A | FAIL |
|
|
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson 110.14- Dissimilar metals shall have an identified connector at splice. Aluminum/copper range wire in panel and receptacle. 210.8- washer receptacle located with in 6' of a sink shall have GFCI protection. Up bath receptacles shall have GFCI protection. Powder bath receptacle not working. 300.15- Box in garage shall be a cover. 404.9(A), 406.6- Switch and receptacle covers shall be in place at time of final.
|
ELE17-00877
| Final | 10/19/2017 | 10/20/2017 | 10/20/2017 11:17:37 AM | A | FAIL |
|
|
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson 110.14- Dissimilar metals shall have identified connector at splice. Aluminum/copper range wire in panel and receptacle. 210.8- Washer receptacle located with in 6' of a sink and shall have GFCI protection. * House staged unable to test all outlets. * Secure panel cover with all screws provided.
|
ELE17-02531
| Final | 10/19/2017 | 10/20/2017 | 10/20/2017 10:05:16 AM | A | FAIL |
|
|
code 4224 any ? call BILL ###-#### Phone #: ###-#### Inspection requested via web by Bob Glenn 404.9 (A), 406.6- Switch and receptacle faceplates shall be installed at time of final. 25 to 30 face plates off at time of inspection.
|
ELE17-02794
| Final | 10/19/2017 | 10/20/2017 | 10/20/2017 9:19:29 AM | A | PASS |
|
|
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|