Inspections for the day of: Friday, October 20, 2017.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03405 Final10/18/201710/20/201710/20/2017 2:07:44 PMPPASS
Please call Kathy 30 mins prior to arrival. ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby...replaced internal panel with same size as existing..job complete...ok to final
ELE17-01572 Final10/19/201710/20/201710/20/2017 1:57:28 PMPPASS
Residential final.

Late as possible please.
Thank you,
Lonnie Phone #: ###-#### Inspection requested via web by Lonnie Sorichta...ok to final
ELE17-03475 Rough-In Permanent Service10/20/201710/20/201710/20/2017 1:00:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn....rough ok to cover...p/s u/g new ok
ELE17-02861 Final10/20/201710/20/201710/20/2017 12:19:53 PMPPASS
Jon-permit was for 200 amp-perm service passed but had no final Phone #: ###-####..ok to final
ELE17-02748 Final10/20/201710/20/201710/20/2017 12:18:45 PMPPASS
Jon-permit was for 200 amp-perm service passed but had no final Phone #: ###-####..

ok to final
ELE17-01935 Final10/20/201710/20/201710/20/2017 11:51:50 AMANR
Please call Von 1/2 hour prior to arrival. Phone #: ###-#### Inspection requested via web by Buster Bowen...concrator has things to finish and safe off for core and shell final
ELE17-02206 Rough-In Permanent Service10/19/201710/20/201710/20/2017 10:47:13 AMAPASS
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson...rough ok to cover...p/s u/g new ok 5 meters
ELE17-03475 Rough-In Permanent Service10/19/201710/20/201710/20/2017 9:50:13 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn....1) small appliance/kitchen circuit can not serve any other outlets but counter top, dining, similiar areas, etc. 210.52(B)- not hallway outlet...2) barriers need placed on service entrance conductors-408.3(A)(2)
ELE17-01829 Final10/19/201710/20/201710/20/2017 9:00:39 AMAPASS
I set up two others at this address Phone #: ###-#### Inspection requested via web by Steve VanWinkle....ul listing and disconnect ok to final
ELE17-01660 Final10/19/201710/20/201710/20/2017 9:00:13 AMAPASS
with 2 others at this location Phone #: ###-#### Inspection requested via web by Steve VanWinkle...ul listing and disconnect ok to final
ELE17-03427 Electrical Rough-In10/18/201710/20/201710/20/2017 8:58:56 AMAPASS
Teresa would like a 30 minute heads up ###-####. If you have any questions please feel free to call Jake ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan...existing outlets moved up, u/c lights added, can lights turned into pendants, circuit extension for range hood...ok to cover
ELE14-02391 Final10/19/201710/20/201710/20/2017 8:21:17 AMAPASS
Aging, I will set up another inspection for Volvo at the same location. Phone #: ###-#### Inspection requested via web by Steve VanWinkle..ok to final
ELE14-02488 Final10/19/201710/20/201710/19/2017 1:22:03 PMPPASS
Aging .May already be out of business?
Phone #: ###-#### Inspection requested via web by Steve VanWinkle...out of business signed removed...final to close permit
ELE14-02273 Final10/19/201710/20/201710/19/2017 12:50:53 PMAPASS
Aging, They may already be gone and out of business? Phone #: ###-#### Inspection requested via web by Steve VanWinkle...sign no longer there...final to close permit