FIR17-00438
| INSP-Final Inspection | 10/19/2017 | 10/20/2017 | 10/20/2017 4:20:10 PM | P | PASS |
|
|
Fire alarm inspection complete per scope of work associated with this permit. A new fire alarm permit will be submitted for future work, Smoke detectors/heat detectors in clean room area will be included on new permit submission.
|
BLD17-00669
| FIRE-Final Inspection | 10/20/2017 | 10/20/2017 | 10/20/2017 3:27:36 PM | P | FAIL |
|
|
Install addressing on exterior of building. In-duct detector needs to be tested for HVAC unti shutdown. Double key deadbolt with indicator or lever type door hardware needs to be installed in place of the thumbturn deadbolt assembly currently in place.
|
FIR17-00326
| INSP-Sprinkler Rough-in | 10/20/2017 | 10/20/2017 | 10/20/2017 2:33:46 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
|
FIR17-00418
| INSP-Sprinkler Rough-in | 10/20/2017 | 10/20/2017 | 10/20/2017 2:33:04 PM | P | CANC |
|
|
Inspection request was for a rough to cover inspection for fire sprinklers, not fire alarms, this inspection request is cancelled.
|
FIR17-00147
| INSP-Final Inspection | 10/19/2017 | 10/20/2017 | 10/20/2017 2:00:25 PM | P | CANC |
|
|
Coordination needs to happen between contractors/building managers of Boise Center on the Grove as well as City Center Plaza Districts for this inspection to be completed. This request is cancelled.
|
FIR16-00268
| INSP-Final Inspection | 10/20/2017 | 10/20/2017 | 10/20/2017 1:51:21 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work passed/complete.
|
FIR16-00293
| INSP-Final Inspection | 10/18/2017 | 10/20/2017 | 10/20/2017 1:47:56 PM | P | PASS |
|
|
Final fire alarm inspection passed/complete.
|
BLD17-03751
| FIRE-Final Inspection | 10/19/2017 | 10/20/2017 | 10/20/2017 12:41:08 PM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is mounted with a current inspection tag. Final life fire safety inspection passed/complete.
|
FIR17-00308
| INSP-Final Inspection | 10/20/2017 | 10/20/2017 | 10/20/2017 12:07:11 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
BLD17-01813
| FIRE-Final Inspection | 10/19/2017 | 10/20/2017 | 10/20/2017 11:12:13 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common area's with current inspection tags. Final life fire safety inspection for area of work passed/complete.
|
FIR17-00365
| INSP-Sprinkler Rough-in/Hydro | 10/19/2017 | 10/20/2017 | 10/20/2017 10:21:40 AM | A | PASS |
|
|
Hydrostatic test for underground supply complete.
|
FIR17-00587
| INSP-Sprinkler Rough-in | 10/19/2017 | 10/20/2017 | 10/20/2017 10:04:29 AM | A | PASS |
|
|
Hydrostatic test for underground supply complete.
|
FIR16-00784
| INSP-Final Inspection | 10/19/2017 | 10/20/2017 | 10/20/2017 9:42:58 AM | A | FAIL |
|
|
Signal sync issue needs to be repaired. Smoke detector in the northeast corridor exit needs to be relocated to be 36 inches away from return air. Annual inspection needs to be completed on fire sprinkler system.
|
BLD17-02522
| FIRE-Final Inspection | 10/19/2017 | 10/20/2017 | 10/20/2017 8:49:44 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is in common area with a current inspection tag. Final life fire safety inspection passed/complete.
|
FIR17-00587
| INSP-Sprinkler Rough-in/Hydro | 10/19/2017 | 10/20/2017 | 10/20/2017 8:31:34 AM | A | CANC |
|
|
Duplicate inspection request, this request is cancelled.
|
FIR16-00284
| INSP-Sprinkler Rough-in/Hydro | 10/19/2017 | 10/20/2017 | 10/20/2017 8:30:31 AM | A | PASS |
|
|
24 hour air test complete.
|