ELE98-02122
| INSP - Electrical Rough-In | 10/20/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | A | PART |
|
|
10/21/98 315 - SARAH ###-#### r/i 2nd floor made note to contractor NEC 300-4 for MC Cable
|
ELE98-03554
| INSP - Electrical Rough-In | 10/20/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | A | PART |
|
|
10/21/98 315 - MARK ###-#### R/I INSP ..trans jms.. ok
|
ELE98-03630
| INSP - Final | 10/21/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | A | FAIL |
|
|
10/21/98 315 - ###-#### TEMP POLE cor. posted 250-83(c) and $42.00 fee due
|
ELE98-03664
| INSP - Final | 10/20/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | A | PASS |
|
|
10/21/98 315 - RON ###-#### TEMP POLE IS IN ALLEYWAY IN BACK OF LOT ..tr ok
|
ELE98-03671
| INSP - Electrical Rough-In | 10/21/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | P | FAIL |
|
|
10/21/98 315 - U/G FEEDER PIPES FOR T-HANGAR C--MIKE PAGER ###-#### alled contractor he will request a am inspection because gste was locked
|
ELE98-03655
| INSP - Final | 10/21/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | P | PASS |
|
|
10/21/98 315 - roy kay ###-#### perm insp p/s o/h rec.
|
ELE98-03363
| INSP - Electrical Rough-In | 10/21/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | P | PART |
|
|
10/21/98 315 - DAVE ###-#### concrete encased electrode and 01 ok ì
|
ELE98-03364
| INSP - Electrical Rough-In | 10/21/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | P | PART |
|
|
10/21/98 315 - DAVE ###-#### concrete encased electrode and 01 ok ì
|
ELE98-03532
| INSP - Electrical Rough-In | 10/20/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | P | FAIL |
|
|
10/21/98 315 - DOROTHY WARE ###-#### cor. posted 250-81 grd within 5 ft 250-60, 61 insulated neutral to range u bolt or guy kit and 2 inch rigid or imc for mast
|
ELE98-02120
| INSP - Electrical Rough-In | 10/21/1998 | 10/21/1998 | 10/21/1998 12:00:00 AM | P | PART |
|
|
10/21/98 315 - NANCY- ###-#### FOR CEILING INSP and parking lot u/g ok
|