Inspections for the day of: Thursday, October 21, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-02302 Final10/20/200410/21/200410/21/2004 12:00:00 AMAPASS
jessie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
final ok 10/21/2004 12:25:10 PM
ELE04-03250 Electrical Rough-In10/20/200410/21/200410/21/2004 12:00:00 AMAPART
Phone #: ###-#### Internet Inspection Request from: Jan Rice
underground ok feeders 10/21/2004 12:25:42 PM
ELE04-02656 Electrical Rough-In10/20/200410/21/200410/21/2004 12:00:00 AMAFAIL
ground work -regina; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ufer encasement ok, need to have water pipe ground 5' from entrance to building 10/21/2004 12:27:16 PM
ELE04-03160 Electrical Rough-In10/20/200410/21/200410/21/2004 12:00:00 AMAPART
steve; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ri walls only ok 10/21/2004 12:24:53 PM
ELE04-03089 Electrical Rough-In10/20/200410/21/200410/21/2004 12:00:00 AMAPART
STEVE COVER FOR WALLS IN DINNING ROOM & UNDERGROUND DRIVE THRU; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
ri walls in dining room only ok, underground ok 10/21/2004 12:28:17 PM
ELE04-03185 Rough-In Permanent Service10/21/200410/21/200410/21/2004 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn
ri ok
p/s u/g n ok 10/21/2004 3:47:06 PM
ELE04-03184 Rough-In Permanent Service10/21/200410/21/200410/21/2004 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn
ri ok
p/s u/g n ok 10/21/2004 3:47:27 PM
ELE04-03117 Electrical Rough-In10/21/200410/21/200410/21/2004 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 10/21/2004 at 8:21:43 AM. Contact: ###-####.
not ready they should have canceled 10/21/2004 6:09:49 PM
ELE04-03237 Final10/21/200410/21/200410/21/2004 12:00:00 AMPNR
BILL; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
not ready should have been canceled 10/21/2004 4:09:44 PM
ELE04-03263 Permanent Service10/21/200410/21/200410/21/2004 12:00:00 AMPCANC
steven - ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
this was a confrence with the homeowner. talked about grounding, bonding, clearences, mast hights. 10/21/2004 1:51:40 PM
ELE04-03237 Electrical Rough-In10/21/200410/21/200410/21/2004 12:00:00 AMPFAIL
240.4D-#10awg conductors shall be protected at 30amps
300.5A-no inspection was done to verfy the burial depth
250.52A5-ground rods are required for this installation
200.7C1-grounded conductors shall be reidentified for use as ungrounded conductors