ELE04-02302
| Final | 10/20/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | A | PASS |
|
|
jessie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
final ok 10/21/2004 12:25:10 PM
|
ELE04-03250
| Electrical Rough-In | 10/20/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Jan Rice
underground ok feeders 10/21/2004 12:25:42 PM
|
ELE04-02656
| Electrical Rough-In | 10/20/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | A | FAIL |
|
|
ground work -regina; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ufer encasement ok, need to have water pipe ground 5' from entrance to building 10/21/2004 12:27:16 PM
|
ELE04-03160
| Electrical Rough-In | 10/20/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | A | PART |
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ri walls only ok 10/21/2004 12:24:53 PM
|
ELE04-03089
| Electrical Rough-In | 10/20/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | A | PART |
|
|
STEVE COVER FOR WALLS IN DINNING ROOM & UNDERGROUND DRIVE THRU; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
ri walls in dining room only ok, underground ok 10/21/2004 12:28:17 PM
|
ELE04-03185
| Rough-In Permanent Service | 10/21/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Bob Glenn
ri ok
p/s u/g n ok 10/21/2004 3:47:06 PM
|
ELE04-03184
| Rough-In Permanent Service | 10/21/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Bob Glenn
ri ok
p/s u/g n ok 10/21/2004 3:47:27 PM
|
ELE04-03117
| Electrical Rough-In | 10/21/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 10/21/2004 at 8:21:43 AM. Contact: ###-####.
not ready they should have canceled 10/21/2004 6:09:49 PM
|
ELE04-03237
| Final | 10/21/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | P | NR |
|
|
BILL; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
not ready should have been canceled 10/21/2004 4:09:44 PM
|
ELE04-03263
| Permanent Service | 10/21/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | P | CANC |
|
|
steven - ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
this was a confrence with the homeowner. talked about grounding, bonding, clearences, mast hights. 10/21/2004 1:51:40 PM
|
ELE04-03237
| Electrical Rough-In | 10/21/2004 | 10/21/2004 | 10/21/2004 12:00:00 AM | P | FAIL |
|
|
240.4D-#10awg conductors shall be protected at 30amps
300.5A-no inspection was done to verfy the burial depth
250.52A5-ground rods are required for this installation
200.7C1-grounded conductors shall be reidentified for use as ungrounded conductors
|